Data Sheet
www.Fisher.com
Fisherr LCP100 Local Control Panel
The LCP100 local control panel is used in conjunction
with the FIELDVUE™ DVC6200 SIS digital valve
controller to manually open, close, or test a safety
shutdown valve. The LCP100 has three protected
pushbuttons to allow the user to open, close or test
the safety valve. There are also three lights to visually
indicate if the valve is open, closed, or locked in safety
and ready for reset.
Features
Reliability
n Rugged Enclosure—The filled polyester enclosure,
encapsulated electronics, pushbuttons, and lights
are designed to withstand harsh industrial
environments.
n Proof Testing—The open and close pushbuttons
provide a means to manually perform an offline full
stroke test to help identify dangerous undetected
failures.
n Partial Valve Stroke Test—The test pushbutton
provides a means to manually perform an online
partial stroke test to help improve the diagnostic
coverage factor.
Safety
n Manual Reset—After a safety demand, the DVC6200
SIS will remain locked in the safe state. The manual
reset pushbutton provides user control over when
the valve can return to the normal operating state.
n Lockable Pushbutton Covers—Each pushbutton can
be locked to prevent unauthorized access to the
safety valve operation.
n Safety Certification—The LCP100 contribution to
failure rates is documented in the DVC6200 SIS
safety manual.
FISHER LCP100 LOCAL CONTROL
PANEL, WITH FIELDVUE DVC6200 SIS
DIGITAL VALVE CONTROLLER AND
BETTIS™
ACTUATOR
X0247
Ease of Use
n Loop vs. External Power—The LCP100 can be
powered by the same loop as the DVC6200 SIS or
independently powered by a 24 VDC source.
n Simple Configuration—The DVC6200 SIS setup
wizard automatically configures the LCP100
functions.
Value
n Visual Indication—The LCP100 can be mounted
remote from the valve in an easily accessible
location to view the status and perform periodic
testing.
n Reduce I/O Count—The LCP100 combines
open/closed/readytoreset lights and open/close
pushbuttons into a single field enclosure, thus
eliminating 3 discrete out (DO) and 2 discrete in (DI)
channels from the logic solver.
LCP100 Local Control Panel
D103604X012
Product Bulletin
62.1:LCP100
November 2013