9. Install the plug (1/4 NPT, included in the mounting kit) to the external output pneumatic port A.
10. Using a 5 mm hex wrench, attach the digital valve controller to the GX actuator mounting pad on the side that has
the open pneumatic port. Be sure to place the O‐ring between the digital valve controller's pneumatic output and
the actuator mounting pad. Pneumatic tubing is not required because the air passages are internal to the actuator.
11. Check for clearance between the magnet assembly and the DVC6200 feedback slot.
12. If not already installed, install a vent in the port on the upper diaphragm casing's air supply connection on the
actuator yoke leg.
13. For remote mount applications, proceed to page 13 for DVC6205 base unit mounting. Otherwise, proceed to
Step 2—Connect the Pneumatic Tubing on page 15.
For air‐to‐close GX actuators
Vertically align the magnet assembly so that the center line of the alignment template is lined up as close as possible
with the lower
extreme of the valid travel range on the magnet assembly. The magnet assembly should be positioned
so that the index mark on the pole pieces (back of the DVC6200 housing) is within the valid range on the magnet
assembly throughout the range of travel. See figure 9.
Figure 9. Air‐to‐Close Fisher GX Magnet Assembly Alignment
ALIGNMENT
TEMPLATE
W9219
INDEX MARK
RETAINING
SLOT
FEEDBACK PIECES
VALVE STEM
CONNECTOR
7. Tighten the fasteners and remove the alignment template.
Note
Use a flat end hex key to tighten the mounting assembly fasteners to a torque of 2.37 N•m (21 lbf•in) for 4 mm screws, and
5.08 N•m (45 lbf•in) for 5 mm screws. While tightening the fasteners using the hex key should be sufficient, blue (medium) thread
locker may be used for additional security.