Instruction Manual

Instruction Manual Supplement
D103639X012
DVC6200 Digital Valve Controller
August 2014
9
Command 14: Read Primary Variable Transducer Information
The transducer limits reported in this command are either 420 milliamps, or 0100%, and reflect the units code most
recently supplied in command 44.
Note
The Transducer Serial Number is not applicable to the DVC6200 and is set to “0”.
Byte Format Description Returned Value
Request
Data
bytes
None
Response
Data
Bytes
02 UINT24 Transducer Serial Number 000000
3 Enum Transducer Limits and Minimum Span Units Code From Cmd 44
47 Float Upper Transducer Limit 20mA
811 Float Lower Transducer Limit 4.0mA
1215 Float Minimum Span 1.0mA
Code Class Description
Response
Codes
None