Command 14: Read Primary Variable Transducer Information
The transducer limits reported in this command are either 420 milliamps, or 0100%, and reflect the units code most
recently supplied in command 44.
Note
The Transducer Serial Number is not applicable to the DVC6200 and is set to “0”.
Byte Format Description Returned Value
Request
Data
bytes
None
Response
Data
Bytes
02 UINT24 Transducer Serial Number 000000
3 Enum Transducer Limits and Minimum Span Units Code From Cmd 44
47 Float Upper Transducer Limit 20mA
811 Float Lower Transducer Limit 4.0mA
1215 Float Minimum Span 1.0mA
Code Class Description
Response
Codes
None