Instruction Manual

Instruction Manual Supplement
D103639X012
DVC6200 Digital Valve Controller
August 2014
5
Internal Jumpers And Switches (Optional)
The input to the DVC6200 is determined by the PtPt/MultiDrop switch on the printed wiring board.
The DVC6200 also has a pair of optional “Output” terminals that can either function as a position transmitter or a
discrete switch. Electrical configuration of the output circuit requires the proper setting of a DIP switch on the
DVC6200’s printed wiring board. Additionally, the functional operation of the output circuit must be configured with
the user interface.
Refer to the DVC6200 instruction manual for additional details on the settings of the selection switches.
OUTPUT+
OUTPUT-
X0430
WITH OPTIONAL I/O PACKAGE
X0431
WITHOUT I/O PACKAGE
PT-PT/
MULTI-DROP
SELECTION
X0432
DIP SWITCH FOR
TRANSMITTER/SWITCH
SELECTION
X0427
PT-PT/
MULTI-DROP
SELECTION
Write Protection
There are two Write Protection states for the DVC6200: Not Protected or Protected. Protected prevents configuration
and calibration changes to the instrument. The default setting is Not Protected. Protection is controlled under
software control. Write Protection can be enabled remotely. However, to disable Write Protection to Not Protected,
you must have physical access to the instrument. The procedure will require you to press a button inside the terminal
box when directed by the software as a security measure.