Annex B DVC6200 Parameters as part of a Rosemount 1410 /
1420 WirelessHART Gateway
A FIELDVUE DVC6200 can join a wireless network through the addition of a Rosemount 775 THUM WirelessHART
adapter. The wireless adapter acts both as a HART modem for communications coming to the DVC6200 from
application software and as an independent master issuing commands periodically to the wired device pertaining to
it’s status. This independently gathered status information is relayed back to the Rosemount 1410 or 1420 Wireless
Gateway and is made available to the user either through viewing the HTML interface or via mapping as “Published
Data” parameters via the Gateway’s MODBUS or OPC outputs.
For HART 5 devices the PV, SV, TV, and QV variables can be mapped.
For HART 7 devices up to 8 variables can be mapped.
Configure the THUM as follows:
HART 5 - select PV, SV, TV, and QV
HART 7 - select Process Variables with Variable Status
Choose Variables 0, 1, 2, 4, 6, 8, 9, and 10
Select Yes if changes are required
Both HART 5 and HART 7 - select Device Status
Navigate to Configure > Manual Setup
Under the Wired Device tab select Configure HART Polling
FOR PRIMARY DEVICE INFORMATION:
FOR SECONDARY DEVICE INFORMATION:
Wired Device tab