Instruction Manual
Instruction Manual Supplement
D103639X012
DVC6200 Digital Valve Controller
August 2014
16
CommonPractice Commands
The DVC6200 field device supports the following common practice commands:
Supported Commands
Command 33: Read Device Variables
Command 35: Write Primary Variable Range Values
Command 42: Perform Master Reset
Command 44: Write PV Units Code
Command 50: Read Dynamic Variable Assignments
Command 51: Write Dynamic Variable Assignments
Command 52: Set Device Variable Zero
Command 53: Set Device Variable Units
Command 54: Read Device Variable Information
Command 59: Write Number of Response Preambles
Burst Mode
This field device does not support Burst Mode when operating in HART 7 mode.
This field device supports Burst Mode and the following commands when it is operating in HART 5 mode:
Command 107: Write Burst Mode Variables
Command 108: Write Burst Mode Command Number
Command 109: Burst Mode Control
Catch Device Variable
This field device does not support Catch Device Variable.