Data Sheet
DVC6200 Digital Valve Controller
D103423X012
Product Bulletin
62.1:DVC6200 HC
September 2013
4
Specifications (continued)
Electrical Housing
CSA— Type 4X, IP66 ATEX— IP66
FM— Type 4X, IP66 IECEx— IP66
Other Classifications/Certifications
Natural Gas Certified, Single Seal Device— CSA, FM,
ATEX, and IECEx
FSETAN—Federal Service of Technological, Ecological
and Nuclear Inspectorate (Russia)
GOST-R— Russian GOST-R
INMETRO— National Institute of Metrology, Quality and
Technology (Brazil)
KGS— Korea Gas Safety Corporation (South Korea)
NEPSI— National Supervision and Inspection Centre for
Explosion Protection and Safety of Instrumentation
(China)
PESO CCOE— Petroleum and Explosives Safety
Organisation - Chief Controller of Explosives (India)
TIIS— Technology Institution of Industrial Safety (Japan)
Not all certifications apply to all constructions. Contact
your Emerson Process Management sales office for
classification/certification specific information.
Connections
Supply Pressure: 1/4 NPT internal and integral pad for
mounting 67CFR regulator
Output Pressure: 1/4 NPT internal
Tubing: 3/8‐inch recommended
Vent: 3/8 NPT internal
Electrical: 1/2 NPT internal, M20 adapter optional
Actuator Compatibility
Stem Travel (Sliding‐Stem Linear)
Minimum: 6.35 mm (0.25 inch)
Maximum: 606 mm (23‐7/8 inches)
Shaft Rotation (Quarter‐Turn Rotary)
Minimum: 45_
Maximum: 90_
Weight
Aluminum: 3.5 kg (7.7 lbs)
Stainless Steel: 8.6 kg (19 lbs)
Construction Materials
Housing, module base and terminal box:
A03600 low copper aluminum alloy (standard),
Stainless Steel (optional)
Cover: Thermoplastic polyester
Elastomers: Nitrile (standard)
Options
J Supply and output pressure gauges or J Tire valves
J Integral mounted filter regulator J Low‐Bleed Relay
J Extreme Temperature J Natural Gas Certified, Single
Seal Device
J Remote Mount
(8)
J Stainless Steel
J Integral 4‐20mA Position Transmitter
(1)(9)
J Integral Limit Switch
(1)(10)
Additional Information
For additional information go to www.FIELDVUE.com or
contact your Emerson Process Management sales office.
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.
1. Only available with DVC6200 HW2.
2. Values listed are applicable for DVC6200 HW 1. For HW 2: Minimum Voltage Available at Instrument Terminals must be 9.5 VDC for analog control, 10 VDC for HART communication.
3. The pressure/temperature limits in this document and any other applicable code or standard should not be exceeded.
4. Normal m
3
/hour - Normal cubic meters per hour at 0_C and 1.01325 bar, absolute. Scfh - Standard cubic feet per hour at 60_F and 14.7 psia.
5. Values at 1.4 bar (20 psig) based on a single‐acting direct relay; values at 5.5 bar (80 psig) based on double‐acting relay.
6. Temperature limits vary based on hazardous area approval.
7. Not applicable for travels less than 19 mm (0.75 inch) or for shaft rotation less than 60 degrees. Also not applicable for digital valve controllers in long‐stroke applications.
8. 4‐conductor shielded cable, 18 to 22 AWG minimum wire size, in rigid or flexible metal conduit, is required for connection between base unit and feedback unit.
9. 4‐20 mA output, isolated; Supply Voltage: 8‐30 VDC; Fault Indication: offrange high or low; Reference Accuracy: 1% of travel span.
10. One isolated switch, configurable throughout the calibrated travel range or actuated from a device alert; Off State: 0 mA (nominal); On State: up to 1 A; Supply Voltage: 30 VDC maximum;
Reference Accuracy: 2% of travel span.
Emerson Process Management
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Chatham, Kent ME4 4QZ UK
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
E 2009, 2013 Fisher Controls International LLC. All rights reserved.
Fisher, FIELDVUE, and ValveLink are marks owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co.
Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART is a mark owned by the
HART Communication Foundation. All other marks are the property of their respective owners.
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.