Figure 26. Typical FM Nameplate
Figure 27. FM Installation Drawing
GE10683‐D
HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION
CLASS I, DIV. 1, GROUPS A,B,C,D
CLASS I ZONE 0 Aex ia IIC
DVC2000
XMTR
MAIN
LS1
LS2
FM APPROVED
BARRIER
XMTR
MAIN
LS1
LS2
PARTITIONED AREA
DETAIL 1
INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC)
AND ANSI/ISA RP12.6.
BARRIERS MUST BE CONNECTED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE
APPARATUS TO ASSOCIATED APPARATUS, NOT SPECIFICALLY EXAMINED IN
SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE
VOLTAGE (Vmax) AND THE CURRENT (Imax) OF THE INTRINSICALLY SAFE
APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Voc) AND
CURRENT (Isc) DEFINED BY THE ASSOCIATED APPARATUS. IN ADDITION, THE
SUM OF THE MAXIMUM UNPROTECTED CAPACITANCE (Ci) AND INDUCTANCE
(Li) OF EACH INTRINSICALLY SAFE APPARATUS, AND THE INTERCONNECTING
WIRING, MUST BE LESS THAN THE ALLOWABLE CAPACITANCE (Ca) AND
INDUCTANCE (La) DEFINED BY THE ASSOCIATED APPARATUS. IF THESE
CRITERIA ARE MET, THEN THE COMBINATION MAY BE CONNECTED.
FORMULAS - Vmax > Voc, or Vt, Ci + Ccable < Ca, Pi > Po, or Pt
Imax > Isc, or It, Li + Lcable < La
ENTITY PARAMETERS FOR EACH I.S. CIRCUIT ARE AS FOLLOWS:
WHERE MULTIPLE IS CIRCUITS ARE USED:
EACH I.S. CIRCUIT MUST BE SHIELDED TWISTED PAIR CABLE.
I.S. CIRCUITS MUST ENTER ENCLOSURE VIA CONDUIT ENTRIES
AS SPECIFIED IN DETAIL 1.
CABLE INSULATION AND SHIELD MUST EXTEND TO WITHIN PARTITIONED
AREA (SEE DETAIL 1).
XMTR, LS1, AND LS2 CIRCUITS ARE OPTIONAL.
CLASS I, DIV 2 APPLICATIONS MUST BE INSTALLED AS SPECIFIED IN NEC ARTICLE 501‐4(B).
EQUIPMENT AND FIELD WIRING IS NON‐INCENDIVE WHEN CONNECTED TO APPROVED
BARRIERS WITH ENTITY PARAMETERS.
MAXIMUM SAFE AREA VOLTAGE SHOULD NOT EXCEED 250 Vrms.
RESISTANCE BETWEEN BARRIER GROUND AND EARTH GROUND MUST BE LESS THAN ONE OHM.
IF HAND‐HELD COMMUNICATOR OR MULTIPLEXOR IS USED, IT MUST BE FM APPROVED
WITH ENTITY PARAMETERS AND INSTALLED PER THE MANUFACTURER'S CONTROL DRAWING.
CIRCUIT
XMTR
MAIN
LS1
LS2
IMAX(Ii)
100mA
130mA
76mA
76mA
VMax (Ui)
28Vdc
30Vdc
16Vdc
16Vdc
Li
0 mH
0.55 mH
0 mH
0 mH
PMAX
1W
1W
1W
1W
Ci
5nF
10.5nF
5nF
5nF
FM APPROVED
BARRIER
FM APPROVED
BARRIER
FM APPROVED
BARRIER
THE APPARATUS ENCLOSURE CONTAINS ALUMINUM
AND IS CONSIDERED TO CONSTITUTE A POTENTIAL
RISK OF IGNTION BY IMPACT OR FRICTION. CARE
MUST BE TAKEN DURING INSTALLATION AND USE TO
PREVENT IMPACT OR FRICTION.
WARNING