Quick Start Guide

Quick Start Guide
D103203X012
DVC2000 Digital Valve Controller
April 2014
31
Table 4. EMC Summary Results—Immunity
Port Phenomenon Basic Standard Test Level Performance Criteria
(1)
Enclosure
Electrostatic discharge
(ESD)
IEC 61000‐4‐2
6 kV contact
8 kV air
B
Radiated EM field IEC 61000‐4‐3
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
A
Rated power frequency
magnetic field
IEC 61000‐4‐8 30 A/m at 50 Hz, 60 sec A
I/O signal/control
Burst (fast transients) IEC 61000‐4‐4
$1 kV
A
Surge IEC 61000‐4‐5
$1 kV (line to ground only, each)
B
Conducted RF IEC 61000‐4‐6 150 kHz to 80 MHz at 10 Vrms A
Performance criteria is + / - 1% effect.
1. A = No degradation during testing. B = Temporary degradation during testing, but is self‐recovering.