Instruction Manual

Maintenance and Troubleshooting
April 2014
Instruction Manual
D103176X012
69
Figure 6‐2. Mounting Frame Assembly
INTERCONNECT
BOARD SCREW (1)
I/P CONVERTER SCREW HOLES (4)
(SCREWS NOT SHOWN)
MOUNTING FRAME SCREW HOLES (2)
(SCREWS NOT SHOWN)
I/P BOARD SCREW (1)
PNEUMATIC
RELAY SCREWS (2)
MANIFOLD
ASSEMBLY
INTERCONNECT
BOARD
W9103
Assembly
1. Replace the short conductive gasket (key 24) if necessary.
2. Place the O-ring seal (key 32) into the groove where the feedback sensor extends out through the housing.
Note
The proper placement of this O-ring is critical to maintaining proper ingress protection.
3. Place the termination/sensor board in the housing, taking care not to pinch the O-ring seal.
4. Tighten the 3 fasteners (keys 11 and 15).
5. Place the long conductive gasket (key 29) in the terminal barrier (key 36) as shown in figure 6‐3.
6. Snap the terminal barrier to the terminal board assembly and place the conductive gasket along the perimeter of
the DVC2000 housing.
7. Install the I/P and Interconnect boards to the Mounting Frame. Do not tighten the self-tapping screws on the
interconnect board (key 42) at this point. The two wires must be inserted into the plastic wire retainer on the
mounting frame (Intrinsically Safe units).
8. Install the Mounting Frame to the housing, making sure that the O-rings (keys 45 and 51) are in place.
9. Install the Main Electronics to the mounting frame, making sure that the pressure sensor seal (key 16) is in place.