Instruction Manual

Instruction Manual
D103176X012
Detailed Setup and Calibration
April 2014
40
Setting Protection
Field Communicator Setup & Diag > Detailed Setup > Protection (1-2-2)
Some setup parameters may require changing the protection with the Field Communicator.
Two levels of protection are available:
DNone—Neither setup nor calibration is protected. Allows changing calibration and setup parameters.
DConfig & Calib—Both setup and calibration are protected. Prohibits changing calibration and protected setup
parameters.
Table 4‐2 lists configurable parameters in the instrument and the requirements for modifying these parameters, in
terms of instrument mode and protection.
Table 4‐2. Conditions for Modifying FIELDVUE DVC2000 Digital Valve Controller Parameters
Parameters
In Service/
Config Protected
In Service/
Config Unprotected
Out of Service/
Config Protected
Out of Service/
Config Unprotected
Control Mode
Restart Ctrl Mode
Burst Mode Enable
Burst Mode Command
Protection
- - -
- - -
n
- - -
n
- - -
- - -
n
- - -
n
n
- - -
n
- - -
n
n
n
n
n
n
HART Tag
Message
Descriptor
Date
Valve Serial Num
Inst Serial Num
Polling Address
- - -
- - -
- - -
- - -
- - -
- - -
- - -
n
n
n
n
n
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
n
n
n
n
n
n
n
Max Supply Pressure
Zero Ctrl Signal
- - -
- - -
- - -
- - -
- - -
- - -
n
n
Analog In Units
Input Range High
Input Range Low
Pressure Units
Temp Units
- - -
- - -
- - -
- - -
n
- - -
- - -
- - -
- - -
n
- - -
- - -
- - -
- - -
n
n
n
n
n
n
Tuning Set
Prop Gain
Velocity Gain
MLFB Gain
Input Char
Define Custom Char
Set Pt Filter Time
- - -
- - -
- - -
- - -
- - -
- - -
- - -
n
n
n
n
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
n
n
n
n
n
n
n
Tvl Limit High
Tvl Limit Low
Tvl Cutoff High
Tvl Cutoff Low
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
n
n
n
n
n—indicates parameter may be modified for instrument mode and protection shown.
-Continued-