Instruction Manual

Instruction Manual
D103176X012
Installation
April 2014
20
Wire the digital valve controller as follows:
1. Remove the main instrument cover.
2. Route the field wiring into the terminal box through the conduit connection. When applicable, install conduit using
local and national electrical codes that apply to the application.
3. Connect the control system output card positive wire “current output” to the +11 terminal. Connect the control
system output card negative (or return) wire “current output” to the -12 terminal.
4. Two ground terminals are available for connecting a safety ground, earth ground, or drain wire. These ground
terminals are electrically identical. Make connections to these terminals following national and local codes and
plant standards.
5. Replace the cover if the local interface is not being used for configuration or calibration.
Options Boards
All three options circuits (transmitter, switch 1 and switch 2) control current from an external power source similar to
the operation of a 2-wire transmitter.
Limit Switches
On units that are supplied with integral limit switches, additional terminals provide the field wiring connection point.
The limit switches are isolated from each other and from the digital valve controller's primary feedback. If only one
switch is to be used, you must use channel 1. Although electrically isolated per Intrinsic Safety requirements, channel 2
derives its power from channel 1. Therefore channel 2 cannot be used alone.
Wire the limit switches as follows:
1. Remove the main instrument cover.
2. Route the field wiring into the terminal box through the conduit connection. When applicable, install conduit using
local and national electrical codes that apply to the application.
3. Connect the control system input card positive wire “switch input” to the +41 terminal. Connect the control system
input card negative wire “switch input” to the -42 terminal. Refer to figure 2‐15.
4. If a second switch is to be used, connect the control system input card positive wire “switch input” to the +51
terminal. Connect the control system input card negative wire “switch input” to the -52 terminal.
5. Proceed to the Basic Setup section to configure the switch action.
6. Replace the cover if the local interface is not being used for configuration or calibration.
HART
COMMUNICATION
TERMINATION
POINTS
+31/ -32 (TRANSMITTER)
+11/ -12 (LOOP)
+41/ -42 (SWITCH 1)
+51/ -52 (SWITCH 2)
W8838
Figure 2‐15. Loop, Transmitter, and Limit Switch Terminals