Data Sheet

DVC2000 Digital Valve Controller
D103167X012
Product Bulletin
62.1:DVC2000
March 2014
7
Figure 3. Dimensions for FIELDVUE DVC2000 Digital Valve Controller
mm
(INCH)
90
(3.55)
E0916-1
106
(4.17)
165.6
(6.52)
Table 1. EMC Summary Results—Immunity
Port Phenomenon Basic Standard Test Level
Performance
Criteria
(1)
Enclosure
Electrostatic discharge (ESD) IEC 61000-4-2
6 kV contact
8 kV air
B
Radiated EM field IEC 61000-4-3
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
A
Rated power frequency magnetic
field
IEC 61000-4-8 30 A/m at 50 Hz, 60 sec A
I/O signal/control
Burst (fast transients) IEC 61000-4-4
$1 kV
A
Surge IEC 61000-4-5
$1 kV (line to ground only, each)
B
Conducted RF IEC 61000-4-6 150 kHz to 80 MHz at 10 Vrms A
Performance criteria is + / - 1% effect.
1. A = No degradation during testing. B = Temporary degradation during testing, but is self-recovering.
Table 2. Hazardous Area Classifications—CSA (Canada)
Certification Body Certification Obtained Entity Ratings Temperature Code Enclosure Rating
CSA
Intrinsically Safe
 Ex ia IIC T4/T5 per drawing GE12444
 Class I Division 1 GP A,B,C,D per drawing GE12444
(Main Circuit)
Vmax = 30 VDC
Imax = 130 mA
Pi = 1.0 W
Ci = 10.5 nF
Li = 0.55 mH
T4(Tamb 80C)
T5(Tamb 40C)
IP66
Non-incendive
 Class I Division 2 GP A,B,C,D T5
- - - T5(Tamb 80C) IP66
Table 3. Hazardous Area Classifications—FM (United States)
Certification Body Certification Obtained Entity Ratings Temperature Code Enclosure Rating
FM
IS Intrinsically Safe
 Class I Division 1 GP A,B,C,D T4/T5 per drawing GE10683
 Class I Zone 0 AEx ia IIC per drawing GE10683
(Main Circuit)
Vmax = 30 VDC
Imax = 130 mA
Pi = 1.0 W
Ci = 10.5 nF
Li = 0.55 mH
T4(Tamb 80C)
T5(Tamb 40C)
IP66
NI Non-incendive
 Class I Division 2 GP A,B,C,D T5
- - - T5(Tamb 80C) IP66