Instruction Manual

Instruction Manual Supplement
D103261X012
DVC6000/DVC6200 Digital Valve Controllers
February 2011
7
Figure 6. Lock‐in‐Last on Loss of Loop Current and/or Supply ressure for an Assembly with a Double‐Acting Actuator
(Fisher DVC6000 Depicted)
2
3
1
+
-
-+
E
D
F
C
B
A
+
+
-
-
12
7
13
8
12
4‐20 mA
FISHER 377L
TRIP VALVE
24VDC POWER SUPPLY
PHOENIX
SWITCH
MCR‐2SP/UI
FISHER 64
REGULATOR
FISHER 252
AIR/GAS FILTER
AIR SUPPLY
SOLENOID VALVE
(ENERGIZED)
OUTPUT
SUPPLY
OUTPUT
DIGITAL
VALVE
CONTROLLER
NOTE:
THE ASCO 8320 SERIES SOLENOID VALVE OR EQUIVALENT IS APPROPRIATE FOR THIS ASSEMBLY.
1
1
Note
DVC6000 and DVC6200 digital valve controllers require approximately 0.5 seconds to initialize upon power up. During this time,
the digital valve controller cannot provide control. In the case where control of a previously locked valve is restored to a digital
valve controller prior to the completion of initialization, the valve will travel toward its fail‐safe position. A relay with an
engagement deadtime, such as the MCR‐2SP/UI from Phoenix Contact, can be used to delay the release of the locking system until
the digital valve controller has completely initialized. An engagement delay of 1.0 seconds will adequately minimize the dip in
travel.
Note
While the valve is in a locked state, the set point from the digital valve controller may change in response to changes in process
conditions. This change in set point may result in a process bump when control is restored to the digital valve controller.
Related Documents
D Fisher FIELDVUE DVC6000 Digital Valve Controllers Instruction Manual (D102794X012)
D Fisher FIELDVUE
DVC6000 Digital Valve Controllers Quick Start Guide (D102762X012)
D Fisher FIELDVUE DVC6200 Digital Valve Controller Instruction Manual (D103409X012)
D Fisher FIELDVUE DVC6200 Digital Valve Controller Quick Start Guide (D103410X012)
These documents are available from your Emerson Process Management sales office. Also visit our website at
www.FIELDVUE.com.