Instruction Manual

Instruction Manual Supplement
D103783X012
DVC2000 Digital Valve Controller
August 2014
26
ADDITIONAL_STATUS_1 According to Command 48: As defined in the Gateway:
Bit 7 Alert Record Not Empty Alert ALERT_RECORD_HAS_ENTRIES
Bit 6 Auto Tune in Progress AUTO_TUNER_IN_PROGRESS
Bit 5 Calibration in Progress Alert CALIBRATION_IN_PROGRESS
Bit 4 Diagnostics in Progress Alert DIAGNOSTIC_IN_PROGRESS
Bit 3 Pressure Fallback Active Alert PRESSURE_CONTROL_IS_ACTIVE
Bit 2 Reserved
Bit 1 Reserved
Bit 0 Auto Cal in Progress Alert AUTO_TRAVEL_CALIBRATION_IN_PROGRESS
ADDITIONAL_STATUS_2 According to Command 48: As defined in the Gateway:
Bit 7 Reserved
Bit 6 Reserved
Bit 5 Cycle Counter Alert CYCLE_COUNT_ALERT
Bit 4 Travel Accumulator High Alert TRAVEL_ACCUMULATOR_ALERT
Bit 3 Instrument Time is Invalid Alert INSTRUMENT_TIME_IS_INVALID
Bit 2 Alert Record Full Alert ALERT_RECORD_IS_FULL
Bit 1 Offline / Failed Alert OFFLINE_FAILED_ALERT
Bit 0 Reserved
ADDITIONAL_STATUS_3 According to Command 48: As defined in the Gateway:
Bit 7 Reserved
Bit 6 Reserved
Bit 5 Reserved
Bit 4 Reserved
Bit 3 Reserved
Bit 2 Reserved
Bit 1 Integrator Saturated High Alert INTEGRATOR_SATURATED_HIGH
Bit 0 Integrator Saturated Low Alert INTEGRATOR_SATURATED_LOW