Instruction Manual

Instruction Manual
D103434X012
Blocks
November 2014
82
Table B‐5. Analog Input Block Parameter Definitions (Continued)
DescriptionInitial ValueRange
Write Block
Mode
RO /
RW
Index
Number
Label
PARAMETER_NAME
High High Alarm
HI_HI_ALM
33
Data Type: DS‐71
The status of the hi hi alarm and its associated time
stamp.
UNACKNOWLEDGED 33.1 RW
NA
0
ALARM_STATE 33.2 RO 0
TIME_STAMP 33.3 RO 0
SUBCODE 33.4 RO 0
VALUE 33.5 RO 0
High Alarm
HI_ALM
34
Data Type: DS‐71
The status of the hi alarm and its associated time
stamp.
UNACKNOWLEDGED 34.1 RW
NA
0
ALARM_STATE 34.2 RO 0
TIME_STAMP 34.3 RO 0
SUBCODE 34.4 RO 0
VALUE 34.5 RO 0
Low Alarm
LO_ALM
35
Data Type: DS‐71
The status of the lo alarm and its associated time
stamp.
UNACKNOWLEDGED 35.1 RW
NA
0
ALARM_STATE 35.2 RO 0
TIME_STAMP 35.3 RO 0
SUBCODE 35.4 RO 0
VALUE 35.5 RO 0
Low Low Alarm
LO_LO_ALM
36
Data Type: DS‐71
The status of the lo lo alarm and its associated time
stamp.
UNACKNOWLEDGED 36.1 RW
NA
0
ALARM_STATE 36.2 RO 0
TIME_STAMP 36.3 RO 0
SUBCODE 36.4 RO 0
VALUE 36.5 RO 0
Extended Parameter
Output Discrete
OUT_D
37 OOS, MAN OUT_STATE
Data Type: DS‐66
Discrete Output this is true (1) if any of the alarms
selected in ALM_SEL are active.
Alarm Select
ALM_SEL
38 ALL
1: Hi Hi alarm
2: Hi Alarm
3: Lo Lo Alarm
4: Lo Alarm
All bits: 0
Data Type: Bitstring
0=unselected
1=selected
Selected alarms that activate the alarm output.
StdDev
STDDEV
39 RO NA Positive float
Data Type: Float
Standard deviation of the measurement.
Cap StdDev
CAP_STDDEV
40 RO NA Positive float
Data Type: Float
Capability standard deviation, the best deviation
that can be achieved.