Instruction Manual
Instruction Manual
D103434X012
Blocks
November 2014
81
Table B‐5. Analog Input Block Parameter Definitions (Continued)
DescriptionInitial ValueRange
Write Block
Mode
RO /
RW
Index
Number
Label
PARAMETER_NAME
Updated Event
UPDATE_EVT
20
Data Type: DS‐73
This alarm is generated whenever a static parameter
is changed.
UNACKNOWLEDGED 20.1 RW NA
0=Undefined
1
=Acknowledged
2
=Unacknowledged
0=Undefined
UPDATE_STATE 20.2 RO NA
0=Undefined
1
=Update reported
2
=Update not reported
0=Undefined
TIME_STAMP 20.3 RO NA 0
STATIC_REVISION 20.4 RO NA 0
RELATIVE_INDEX 20.5 RO NA 0
Block Alarm
BLOCK_ALM
21
Data Type: DS‐72
The block alarm is used for all configuration,
hardware, connection failure or system problems in
the block. The cause of the alert is entered in the
subcode field.
UNACKNOWLEDGED 21.1 RW
0=Undefined
1
=Acknowledged
2
=Unacknowledged
ALARM_STATE 21.2 RO
0=Undefined
1
=Clear‐reported
2
=Clear‐not reported
3
=Active‐reported
4
=Active‐not reported
TIME_STAMP 21.3 RO
SUBCODE 21.4 RO
VALUE 21.5 RO
Alarm Summary
ALARM_SUM
22
Data Type: DS‐74 Current alert status,
unacknowledged states, unreported states, and
disabled states of the alarms associated with the
function block.
0=clear
0=acknowledged
0=reported
0=enabled
CURRENT 22.1 RO ALL
0: Discrete alarm
1: Hi Hi alarm
2: Hi Alarm
3: Lo Lo Alarm
4: Lo Alarm
7: Block alarm
UNACKNOWLEDGED 22.2 RO ALL
UNREPORTED 22.3 RO ALL
DISABLED 22.4 RW ALL All bits: 0
Acknowledge Option
ACK_OPTION
23 ALL
0: Discrete alarm
1: Hi Hi alarm
2: Hi Alarm
3: Lo Lo Alarm
4: Lo Alarm
7: Block alarm
All bits: 0
Data Type: Bit String
0
=Disable
1
=Enable
Selection of whether alarms associated with the
block will be automatically acknowledged.
Alarm Hysteresis
ALARM_HYS
24 ALL 0 ‐ 50% 0.50%
Data Type: Float
Hysteresis on alarms.
High High Priority
HI_HI_PRI
25 ALL 0 to 15 0
Data Type: Unsigned8
The priority of the hi hi alarm.
High High Limit
HI_HI_LIM
26 ALL OUT_SCALE 0
Data Type: Float
Value of analog input which will generate an alarm.
High Priority
HI_PRI
27 ALL 0 to 15 0
Data Type: Unsigned8
The priority of the high alarm.
Hi Limit
HI_LIM
28 ALL OUT_SCALE 0
Data Type: Float
Value of analog input which will generate an alarm.
Low Priority
LO_PRI
29 ALL 0 to 15 0
Data Type: Unsigned8
The priority of the low alarm.
Low Limit
LO_LIM
30 ALL OUT_SCALE 0
Data Type: Float
Value of analog input which will generate an alarm.
Low Low Priority
LO_LO_PRI
31 ALL 0 to 15 0
Data Type: Unsigned8
The priority of the low low alarm.
Low Low Limit
LO_LO_LIM
32 ALL OUT_SCALE 0
Data Type: Float
Value of analog input which will generate an alarm.
-Continued-