Instruction Manual
Instruction Manual
D103434X012
Configuration
November 2014
40
RTD Sensor
D RTD Sensor—when selected indicates if the RTD readings are out of range or the RTD is incorrectly connected.
D RTD Open—when selected indicates if the RTD is not connected.
Sensor Board
D Instrument Temperature Sensor— when selected indicates if the electronic sensor readings are out of range.
D Sensor Board Processor— when selected indicates if the device cannot communicate properly or other electronic
problem is effecting the processor.
D Hall Sensor— when selected indicates if the Hall Sensor readings are out of range.
Temperature Limit
D Instrument Temperature High— when selected indicates if the device has exceeded the Instrument Temperature
High Limit.
D Instrument Temperature Low— when selected indicates if the device has exceeded the Instrument Temperature
Low Limit.
Input Compensation Error
D Temperature Input Error— when selected indicates if the AO temperature status or RTD status has become “Bad" or
“Uncertain" or the device is not set up correctly to receive AO temperature.
D Upper Fluid Input Error— when selected indicates if the Upper Fluid AO status has become “Bad" or “Uncertain" or
the device is not setup correctly to receive AO density for the Upper Fluid.
D Lower Fluid Input Error— when selected indicates if the Lower Fluid AO status has become “Bad" or “Uncertain" or
the device is not setup correctly to receive AO density for the Lower Fluid.
D Fluid Values Crossed— when selected indicates if the process fluid density values have crossed; the Upper Fluid
density is too close to (0.1 SG), or has become greater than, the Lower Fluid density.
D Invalid Custom Table— when selected indicates if the custom process fluid density table or torque tube table being
used for temperature compensation is invalid.
D Temperature Out of Compensation Range—when selected indicates if the Compensation Temperature has
exceeded the compensation limits.