Instruction Manual

Instruction Manual
D103434X012
Configuration
November 2014
34
Primary Value Percent
PV in %
DI1 Trip Point Settings
Set Channel 1 or 2 of the DI for snap acting control.
DI1 Action—indicate whether the trip point is active on rising or falling level.
DI1 Trip Point—enter the point where DI1 is active.
DI1 Deadband—enter the desired deadband. This is the distance away from the trip point that DI1 clears.
DI1 Readback—indicates the status of the trip point. 0 indicates that DI1 Trip is inactive. 1 indicates DI1 Trip is active.
DI2 Trip Point Settings
DI2 Action—indicate whether the trip point is active on rising or falling level.
DI2 Trip Point—enter the point where DI2 is active.
DI2 Deadband—enter the desired deadband. This is the distance away from the trip point that DI2 clears.
DI2 Readback—indicates the status of the trip point. 0 indicates that DI2 Trip is inactive. 1 indicates DI2 Trip is active.
Options
Select the Options tab (figure 4‐9) to access Write Alarm, Block Alarm, Write Lock, Confirm Time, Communication
Timeout, Function Block Available, Features Selected, Alert Key, Maximum Alerts Allowed, Maximum Alerts Possible, Resource
Block, Transducer Block, and Mode.