Configuration
November 2014
32
Temperature Input—select None, Manual, AO Block, or RTD.
Temperature compensation, when enabled, can come from a manually entered temperature, a temperature from a
fieldbus transmitter (AO block) or a temperature from an RTD.
Temperature for Compensation—the temperature in use for fluid density and torque tube material compensation.
View Fluid Density Table
Select View Fluid Density Table to see information concerning the temperature effect on process fluid density.
Instrument Display
Select the Instrument Display tab (figure 4‐7) to access Display Option, Device Display Primary Value Units, Decimal
Places, Display Primary Value Offset, and Scrolling Message Control.
Figure 4‐7. Configure > Manual Setup > Instrument Display
CONFIGURE
MANUAL
SETUP
INSTRUMENT
DISPLAY TAB
DISPLAY OPTION
DEVICE DISPLAY PRIMARY VALUE UNITS
DECIMAL PLACES
DISPLAY PRIMARY VALUE OFFSET
SCROLLING
MESSAGE CONTROL
MODE
Display Option
Select Primary Value Only, % Range, or Primary Value / % Range to be displayed on the DLC3020f LCD.
Device Display Primary Value Units
Select the units for the device display Primary Value.
Decimal Places
Enter the number of desired decimal places for the device display.