Instruction Manual
Instruction Manual
D103434X012
Configuration
November 2014
25
Section 4 Configuration4‐4‐
Note
The primary transducer block must be set to out of service before the device can be configured.
When using AMS Device Manager 10.1 and earlier go to Target Mode in Block Modes tab to set the primary transducer block in and
out of service. Refer to figure 4‐1.
Figure 4‐1. Block Modes Tab (AMS Device Manager 10.1 and earlier)
SET THE TARGET MODE
TO OUT OF SERVICE
CONFIGURE
BLOCK
MODES
Guided Setup
AMS Device Manager Configure > Guided Setup
Field Communicator Configure > Instrument Setup
Access Instrument Setup from the Guided Setup tab, as shown in figure 4‐2, for sensor, device and process fluid setup.
Follow the prompts to setup the DLC3020f.