Instruction Manual

Instruction Manual
D103434X012
Blocks
November 2014
172
Transducer Block (LCD)
The LCD transducer block is used to configure DLC3020f display properties. It has no affect on the reported PV.
LCD Transducer Block Parameters
D Read/Write Capability: RO ‐ Read Only, RW ‐ Read Write
D Mode: The block mode(s) required to write to the parameter
D Double indentation and shaded Index Number indicates sub‐parameter
Table B‐62. LCD Transducer Block Parameter Definitions
Label
PARAMETER_NAME
Index
Number
RO /
RW
Range Default Value Description
Static Revision
ST_REV
1 RO 0 to 65535 0
Data Type: Uint16
The revision level of the static data. Increments by
one each time a static parameter is written. The
value is reset to 0 whenever a Restart with
Defaults is performed.
Tag Description
TAG_DESC
2 RW NULL
Data Type: String
The description of the block.
Strategy
STRATEGY
3 RW 0 to 65535 0
Data Type: Uint16
Used to help group blocks.
Alert Key
ALERT_KEY
4 RW 0
Data Type: Uint8
The identification number of the plant unit.
Devices in a loop or plant section can be assigned
with a common alert key to aid the operator in
determining location of alerts.
Block Mode
MODE_BLK
5
Data Type: DS‐69
The actual, target, permitted, and normal modes.
Target: The requested block mode
Actual: The current mode of
the block
Permitted: Allowed modes for Target
Normal: Most common mode
for Target
TARGET 5.1 RW
3: AUTO
7: OOS
7: OOS
ACTUAL 5.2 RO NA
PERMITTED 5.3 RW
3:AUTO
7: OOS
NORMAL 5.4 RW 3:AUTO
Block Error
BLOCK_ERR
6 RO Bit 15
Data Type: Bit String
Error status associated with hardware or firmware
for the transducer block.
Display Mode
DISPLAY_MODE
7 RW
1: PV Only
2: % Range
3: PV / % Range
1
Data Type: Enum (1)
Mode the LCD is in.
LCD Unit System
LCD_UNIT_SYSTEM
8 RO
1: English
2: Metric
3: Mixed
2: Metric
Data Type: Enum (1)
The unit system used for the device.
DISPLAY_PV_UNITS
9 RW
1010: Meter
1012: cm
1013: mm
1018: ft.
1019: in.
1342: Percent
1012: cm
Data Type: Enum (2)
PV_DISPLAY units.
DECIMAL_PLACES
10 RW
0: No decimals
1: One
2: Two
3: Three
4: Four
5: As many decimal places
as possible
2
Data Type: Uint8
Ideal decimal places shown. It could be less if
decimal places need to be sacrificed to display
digits left of the decimal point. If that becomes a
problem, consider changing display units.
DISPLAY_OFFSET
11 RW NA 0
Data Type: Float
PV offset applied to display
-Continued-