Instruction Manual
Instruction Manual
D103434X012
Blocks
November 2014
169
Table B‐54. Primary Transducer Block Parameter Definitions (Continued)
DescriptionInitial ValueRangeMode
RO /
RW
Index
Number
Label
PARAMETER_NAME
PRESSURE_SELECT
76 RW OOS
1: None
2: Manual
3: AO
0: None
COMP_PRESSURE
77 RW NA
Data Type: DS‐65
Pressure of upper fluid when upper fluid is a gas
and can effect level measurement.
STATUS
77.1 RO NA NA Data Type: Uint8
VALUE
77.2 RW OOS NA NA
Data Type: Float
Compensation pressure. Writable if
PRESSURE_SELECT is set to manual.
GAS_MOL_WGT
78 RW OOS > 0 NA
Data Type: Float
Molecular weight of gas
DEVICE_HISTORY
79
Data Type: DS‐266
MAX_RECORDED_TEMP
79.1 RO NA ‐ NA
Data Type: Float
Maximum temperature the device has
experienced.
MIN_RECORDED_TEMP
79.2 RO NA ‐ NA
Data Type: Float
Minimum temperature the device has
experience
TIME_OVER_UTL
79.3 RO NA ‐ NA
Data Type: Float
Total number of days the device has been over
80 C
TIME_UNDER_LTL
79.4 RO NA ‐ NA
Data Type: Float
Total number of days the device has been under
‐40 C
TEMP_INTEGRAL
79.5 RO NA ‐ NA
Data Type: Float
The running integral of temperature ‐ time in
DLC_UNITS. TEMPERATURE * day
RUN_TIME
79.6 RO NA ‐ NA
Data Type: Float
The number of days the device has been
running.
TIME_SINCE_RESET
79.7 RO NA ‐ 0
Data Type: Float
Number of days since the last time the
DLC3020f was restarted.
CHAR_ARRAY
80 RW AUTO ‐ ‐
Data Type: Uint8 Array[80]
Reserved
INT_ARRAY
81 RW AUTO ‐ ‐
Data Type: Uint16 Array[20]
Reserved
LONG_ARRAY
82 RW AUTO ‐ ‐
Data Type: Uint32 Array[10]
Reserved
FLOAT_ARRAY
83 RW AUTO ‐ ‐
Data Type: Float Array [21]
Reserved
STRING_RESERVED
84 RW AUTO ‐ ‐
Data Type: Visible String[16]
Reserved
RESERVED
85 RW AUTO ‐ ‐
Data Type: Uint16
Reserved