Table B‐54. Primary Transducer Block Parameter Definitions (Continued)
DescriptionInitial ValueRangeMode
RO /
RW
Index
Number
Label
PARAMETER_NAME
Failed Active
FAILED_ACTIVE
61 *RO
1:
2:
3:
4:
5:
6:
7:
8:
All 0
Data Type: BIT_ENUM (4)
Failed Alert Status 0 = inactive,
1 = active *RW when Simulate jumper and
PWA_SIMULATE is set to 2
Failed Alarm
FAILED_ALM
62
Data Type: DS‐71
Used to report alerts to host system.
UNACKNOWLEDGED 62.1 RW
0: Undefined
1: Acknowledged
2: Unacknowledged
ALARM_STATE 62.2 RO NA
0: Undefined
1: Clear (reported)
2: Clear (not reported)
3: Active (reported)
4: Active (not reported)
TIME_STAMP 62.3 RO NA NA
SUBCODE 62.4 RO NA NA
VALUE 62.5 RO NA NA
Data Type: Float
Value of parameter at alarm time for single
alarm, 0 for multiple alarms
Maintenance Priority
MAINT_PRI
63 RW AUTO 0 to 15 2
Data Type: Uint8
Maintenance alert priority
Maintenance Enable
MAINT_ENABLE
64 RW AUTO
1:
2:
3:
4:
5:
6:
7:
8:
Bit 4
Data Type: BIT_ENUM (4)
Maintenance alert enable. Enable allows
detection of alert. All alerts can be disabled.
Maintenance Suppress
MAINT_MASK
65 RW AUTO
1:
2:
3:
4:
5:
6:
7:
8:
All 0
Data Type: BIT_ENUM (4)
Maintenance alert mask. MASK controls
whether an alert is reported. If alert is enabled
the alert condition is evaluated and the ACTIVE
parameter is updated reflect if alert is active or
not. If the bit is set reporting is suppressed.
Maintenance Active
MAINT_ACTIVE
66 *RO
1:
2:
3:
4:
5:
6:
7:
8:
All 0
Data Type: BIT_ENUM (4)
Maintenance Alert Status
0 = inactive, 1 = active
Maintenance Alarm
MAINT_ALM
67
Data Type: DS‐71
Used to report alerts to host system.
UNACKNOWLEDGED 67.1 RW AUTO
0: Undefined
1: Acknowledged
2: Unacknowledged
ALARM_STATE 67.2 RO NA
0: Undefined
1: Clear (reported)
2: Clear (not reported)
3: Active (reported)
4: Active (not reported)