Instruction Manual
Instruction Manual
D103434X012
Blocks
November 2014
166
Table B‐54. Primary Transducer Block Parameter Definitions (Continued)
DescriptionInitial ValueRangeMode
RO /
RW
Index
Number
Label
PARAMETER_NAME
DI_1_TRIP_PT
44 RW OOS NA 100%
Data Type: Float
Point where DI_1 will trip based on
PRIMARY_VALUE_RANGE
DI_1_DEADBAND
45 RW OOS < 99.5%, > 0% 1%
Data Type: Float
Deadband where a tripped DI_1 will reset.
DI_1_ACTION
46 RW OOS
0: Trip on falling level
1: Trip on rising level
1: Trip on rising
level
Data Type: Enum (1)
D_1 trips on rising or falling level
DI_1_READBACK
47
Data Type: DS‐66
Output of DI_1
STATUS
47.1 RO NA NA NA Data Type: Uint8
VALUE
47.2 RO NA NA NA Data Type: Uint8
DI_2_TRIP_PT
48 RW OOS NA 0%
Data Type: Float
Point where DI_2 will trip based on
PRIMARY_VALUE_RANGE. Range is within
Primary Sensor Range
DI_2_DEADBAND
49 RW OOS < 99.5%, > 0% 1%
Data Type: Float
Deadband where a tripped DI_2 will reset.
DI_2_ACTION
50 RW OOS
0:Trip on falling level
1: Trip on rising level
0: Trip on falling
level
Data Type: Enum (1)
D_2 trips on rising or falling level
DI_2_READBACK
51
Data Type: DS‐66
Output of DI_2
STATUS
51.1 RO NA NA NA Data Type: Uint8
VALUE
51.2 RO NA NA NA Data Type: Uint8
SENSOR_MAJOR_REV
52 RO NA NA NA
Data Type: Uint8
Major firmware revision of sensor board.
SENSOR_MINOR_REV
53 RO NA NA NA
Data Type: Uint8
Minor firmware revision of sensor board.
INSTRUMENT_SN
54 RW OOS NA NULL
Data Type: Visible String [16]
Digital level controller serial number (appears
on nameplate).
SENSOR_ELECT_ID
55 RO NA NA NA
Data Type: Visible String [16]
Unique string identifying the sensor electronics
characterization and test record in the
manufacturing test data base.
TB_DETAILED_STATUS
56 RO Bit 23 ‐ 1 NA
Data Type: BIT_ENUM (4)
Parameter used to show in detail what alerts are
currently set.
Recommended Action
RECOMMENDED_ACTION
57 RO NA NA NA
Data Type: Uint16
Fix for most serious condition
Failed Priority
FAILED_PRI
58 RW AUTO 0 to 15 2
Data Type: Uint8
Failed alert priority
Failed Enable
FAILED_ENABLE
59 RW AUTO
1:
2:
3:
4:
5:
6:
7:
8:
1:
5:
Data Type: BIT_ENUM (4)
Failed alert enable. Enable allows detection of
alert. All alerts can be disabled.
Failed Suppress
FAILED_MASK
60 RW AUTO
1:
2:
3:
4:
5:
6:
7:
8:
All 0
Data Type: BIT_ENUM (4)
Failed alert mask. MASK controls whether an
alert is reported. If alert is enabled the alert
condition is evaluated and the ACTIVE
parameter is updated reflect if alert is active or
not. If the bit is set reporting is suppressed.
-Continued-