Table B‐54. Primary Transducer Block Parameter Definitions (Continued)
DescriptionInitial ValueRangeMode
RO /
RW
Index
Number
Label
PARAMETER_NAME
Lower Density
LOWER_DENSITY
39
Data Type: DS‐65
Lower fluid density.
STATUS
39.1 RO NA NA NA
Data Type: Uint8
Status of lower fluid density value
VALUE
39.2 RO NA NA NA
Data Type: Float
Lower fluid density value
LOWER_TBL
40
Data Type: DS‐257
Density correction table for lower fluid. When
LOWER_FLUID_ TYPE.TYPE is set to custom, this
parameter becomes RW.
COMP_TEMP_1
40.1 *RW OOS 146 to 699 K 288.706K
Data Type: FloatData Type: Float
LOWER_DENSITY_
40.2 *RW OOS > 0 1
COMP_TEMP_2
40.3 *RW OOS 146 to 699 K 310.928K
Data Type: FloatData Type: Float
LOWER_DENSITY_2
40.4 *RW OOS > 0 0.994
COMP_TEMP_3
40.4 *RW OOS 146 to 699 K 366.483K
Data Type: FloatData Type: Float
LOWER_DENSITY_3
40.5 *RW OOS > 0 0.964
COMP_TEMP_4
40.6 *RW OOS 146 to 699 K 422.039K
LOWER_DENSITY_4
40.7 *RW OOS > 0 0.919
COMP_TEMP_5
40.8 *RW OOS 146 to 699 K 477.594K
LOWER_DENSITY_5
40.9 *RW OOS > 0 0.86
COMP_TEMP_6
40.10 *RW OOS 146 to 699 K 533.15K
Data Type: FloatData Type: Float
LOWER_DENSITY_6
40.11 *RW OOS > 0 0.786
COMP_TEMP_7
40.12 *RW OOS 146 to 699 K 588.706K
Data Type: FloatData Type: Float
LOWER_DENSITY_7
40.13 *RW OOS > 0 0.679
COMP_TEMP_8
40.14 *RW OOS 146 to 699 K 0
LOWER_DENSITY_8
40.15 *RW OOS > 0 0
Data Type: FloatData Type: Float
COMP_TEMP_9
40.16 *RW OOS 146 to 699 K 0
LOWER_DENSITY_9
40.17 *RW OOS > 0 0
COMP_TEMP_10
40.18 *RW OOS 146 to 699 K 0
LOWER_DENSITY_10
40.19 *RW OOS > 0 0
Electronics Temperature
ELECTRONICS_TEMP
41 RO NA NA NA
Data Type: Float
Current electronics temperature
SNAP_ACTING_CTRL
42 RW OOS
0: Off
1: On
0: Off
Data Type: Enum (1)
Turns SNAP controller on or off
SNAP_UNITS
43 RW OOS
1010: Meter
1012: cm
1013: mm
1018: ft.
1019: in.
1342: Percent
1342: percent
Data Type: Enum (2)
Units all the SNAP parameters are in.
-Continued-