Blocks
November 2014
163
Table B‐54. Primary Transducer Block Parameter Definitions (Continued)
DescriptionInitial ValueRangeMode
RO /
RW
Index
Number
Label
PARAMETER_NAME
COMP_GAIN_2
33.4 *RW OOS > = 0, < 2 1
Data Type: Float
*Parameter is RW only when
TORQUE_TUBE_MATERIAL is set to custom.
COMP_TEMP_3
33.5 *RW OOS 146 to 699 K 310.928K
COMP_GAIN_3
33.6 *RW OOS > = 0, < 2 0.9982
COMP_TEMP_4
33.7 *RW OOS 146 to 699 K 366.483K
COMP_GAIN_4
33.8 *RW OOS > = 0, < 2 0.9923
COMP_TEMP_5
33.9 *RW OOS 146 to 699 K 422.039K
COMP_GAIN_5
33.10 *RW OOS > = 0, < 2 0.9865
COMP_TEMP_6
33.11 *RW OOS 146 to 699 K 477.594K
COMP_GAIN_6
33.12 *RW OOS > = 0, < 2 0.9808
COMP_TEMP_7
33.13 *RW OOS 146 to 699 K 533.15K
COMP_GAIN_7
33.14 *RW OOS > = 0, < 2 0.9692
COMP_TEMP_8
33.15 *RW OOS 146 to 699 K 588.706K
COMP_GAIN_8
33.16 *RW OOS > = 0, < 2 0.9577
COMP_TEMP_9
33.17 *RW OOS 146 to 699 K 644.261K
COMP_GAIN_9
33.18 *RW OOS > = 0, < 2 0.9385
COMP_TEMP_10
33.19 *RW OOS 146 to 699 K 699.817K
COMP_GAIN_10
33.20 *RW OOS > = 0, < 2 0.9192
Torque Tube Compensation
TORQUE_TUBE_COMP
34 RO NA NA NA Data Type: DS‐65
STATUS
34.1 RO NA NA NA
Data Type: Uint8
Status of the compensated torque tube value.
VALUE
34.2 RO NA NA NA
Data Type: Float
Compensated torque rate being used for PV
compensation
Upper Fluid Type
UPPER_FLUID_TYPE
35
TYPE
35.1 RW OOS
0: Air/None
1: Water
65534: Custom
65535: AO Block
0
Data Type: Enum (2)
Enumeration for the type of upper fluid. Only
writable if in interface mode through parameter
PRIMARY_VALUE_TYPE
BASE_DENSITY
35.2 *RW OOS > 0 0
Base density of fluid at room temperature. If
type is custom, then non temperature
compensated value is entered and saved here.
*Writable but the device will adjust to the
closest value it can on write when it's not a
custom base density they are entering.
CUSTOM_NAME
35.3 *RW OOS NULL
Name of the custom fluid entered. If type is not
custom, then nothing will be shown on a read.
*Writable if type fluid is set to custom.
Upper Density
UPPER_DENSITY
36
Data Type: DS‐65
Upper fluid density. If level mode, upper fluid is
air. E.g. density = 0 in case of SG.
-Continued-