Instruction Manual

Instruction Manual
D103434X012
Blocks
November 2014
159
Table B‐54. Primary Transducer Block Parameter Definitions (Continued)
DescriptionInitial ValueRangeMode
RO /
RW
Index
Number
Label
PARAMETER_NAME
ENG_UNITS 17.3 RO OOS
1010: Meter
1012: cm
1013: mm
1018: ft.
1019: in.
1342: Percent
1342: Percent Data Type: Float
DECIMAL 17.4 RO OOS 2 Data Type: Float
Sensor Serial Number
SENSOR_SN
18 RO NA Data Type: Visible String [32]
Sensor Calibration Method
SENSOR_CAL_METHOD
19 RW OOS
240: Weights
241: Min/Max (Zero
Span)
242: Two Point (Not Zero
Span)
243: Zero Capture
244: Gain Trim
245: Zero Trim
246: Default Gain
247: Simple Two Point
Cal
248: Simple Gain Trim
249: Simple Zero Trim
250: Simple Zero
Capture
251: Factory Default
251: Factory
Default
Data Type: Uint8
Previous calibration method.
Sensor Calibration Location
SENSOR_CAL_LOC
20 RW OOS NA NULL
Data Type: Visible String [32]
Calibration location
Sensor Calibration Date
SENSOR_CAL_DATE
21 RW OOS NA NA
Data Type: DT‐11
Calibration date
SENSOR_CAL_WHO
22 RW OOS NA NULL
Data Type: Visible String [32]
Calibrator
SENSOR_LOG_NAME
23 RW OOS NA Factory Default
Data Type: Visible String [16]
Name of the current log in use as entered by the
user
Sensor Information
SENSOR_INFO
24
Data Type: DS‐268
Sensor information.
Sensor Type
SENSOR_TYPE
24.1 RW OOS
1: 249 Cast
2: 249A
3: 249B
4: 249BF
5: 249C
6: 249K
7: 249L
8: 249N
9: 249P
10: 249V
11: 249VS
12: 249W
13: 259
14: Masoneilan
15: Foxboro Eckardt
16: Yamatake Honeywell
17: Other
255: Unknown
255: Unknown Data Type: Enum (1)
-Continued-