Instruction Manual
Instruction Manual
D103434X012
Blocks
November 2014
158
Table B‐54. Primary Transducer Block Parameter Definitions (Continued)
DescriptionInitial ValueRangeMode
RO /
RW
Index
Number
Label
PARAMETER_NAME
Block Alarm
BLOCK_ALM
8
UNACKNOWLEDGED 8.1 RW
0=Undefined
1=Acknowledged
2=Unacknowledged
0
Data Type: DS‐72
Used to report the BLOCK_ERR alarm to the
host system
ALARM_STATE 8.2 RO NA
0=Undefined
1=Clear‐reported
2=Clear‐not reported
3=Active‐reported
4=Active‐not reported
0
TIME_STAMP 8.3 RO NA NA 0
SUBCODE 8.4 RO NA
Subcode: Bit Number in
BLOCK_ERR
0
VALUE 8.5 RO NA
Value of parameter at
alarm time for a single
alarm, 0 for multiple
alarms
0
Transducer Directory
TRANSDUCER_DIRECTORY
9 RO NA 1,1
Data Type: Array [2] of Unit16
Not used
Transducer Type
TRANSDUCER_TYPE
10 RO NA
Data Type: Uint16
Identifies the type of transducer.
Transducer Error
XD_ERROR
11 RO NA NA 0
Data Type: Uint8
Error code for the transducer block.
Collection Directory
COLLECTION_DIRECTORY
12 RO NA 1,1,1,1,1 1,1,1,1,1
Data Type: Array [5] of Unit32
Not used
PRIMARY_VALUE_TYPE
13 RW OOS
1: Level
2: Interface
1: Level
Data Type: Enum(2) Type of measurement
application (level, interface).
PRIMARY_VALUE
14 Data Type: DS‐65
STATUS
14.1 RO NA NA NA
Data Type: Uint8
Primary value status
VALUE
14.2 RO NA NA NA
Data Type: Float
0% = PRIMARY_VALUE_RANGE. LOWER, 100% =
PRIMARY_ VALUE_RANGE.UPPER
PRIMARY_VALUE_RANGE
15
Data Type: DS‐68
Range the PRIMARY_VALUE can take. Defaults
to displacer length and includes PV_OFFSET
EU_100 15.1 RW OOS NA 14
Data Type: Float
Upper range for PRIMARY_VALUE
EU_0 15.2 RW OOS NA 0
Data Type: Float
Lower range for PRIMARY_VALUE
ENG_UNITS 15.3 RW OOS
1010: Meter
1012: cm
1013: mm
1018: ft.
1019: in.
1012: cm
Data Type: Float
Engineering units for EU_100 & EU_0
DECIMAL 15.4 RW OOS 2 2
Sensor Type
SENSOR_TYPE
16 RW OOS 107 107
Data Type: Uint16
Positive Displacement
Sensor Range
SENSOR_RANGE
17
Data Type: DS‐68
Physical sensor limits
EU_100 17.1 RO OOS NA 14
Data Type: Float
Maximum readable level the digital level
controller can currently read
EU_0 17.2 RO OOS NA 0
Data Type: Float
Minimum readable level the digital level
controller can currently read
-Continued-