Instruction Manual
Instruction Manual
D103434X012
Blocks
November 2014
148
Table B‐42. Arithmetic Function Block Parameter Definitions (Continued)
DescriptionInitial ValueRange
Block
Mode
RO /
RW
Index
Number
Label
PARAMETER_NAME
Input Lo
IN_LO
15
The value used for input whenever IN is below
range.
Input 1
IN_1
16 The first analog input value and status.
Input 2
IN_2
17 The second analog input value and status.
Input 3
IN_3
18 The third analog input value and status.
Range High
RANGE_HI
19 The high limit for IN.
Range Low
RANGE_Lo
20
The low limit for IN. If IN is less than
RANGE_LO, then IN_LO is used.
Bias Input 1
BIAS_IN_1
21 The bias value for IN_1.
Gain Input 1
GAIN_IN_1
22
The proportional gain (multiplier) value for
IN_1
Bias Input 2
BIAS_IN_2
23 The bias value for IN_2.
Gain Input 2
GAIN_IN_2
24
The proportional gain (multiplier) value for
IN_2
Bias Input 3
BIAS_IN_3
25 The bias value for IN_3.
Gain Input 3
GAIN_IN_3
26
The proportional gain (multiplier) value for
IN_3
COMP_HI_LIM
27 High limit for the compensation term.
COMP_LO_LIM
28 Low limit for the compensation term.
ARITH_TYPE
29
Selects the computation to be used as the
block function.
BAL_TIME
30
The time to balance OUT to PRE_OUT after the
block enters Auto mode. It has no effect after
the time expires.
BIAS
31 The bias value.
GAIN
32 The proportional gain (multiplier) value.
Output High Limit
OUT_HI_LIM
33 The maximum output value allowed.
Output Low Limit
OUT_LO_LIM
34 The minimum output value allowed.
UPDATE_EVT
35
This alert is generated by any changes to the
static data.
Block Alarm
BLOCK_ALM
36 Dynamic
Data Type: DS‐72
The read‐only data for an alarm generated by a
change in BLOCK_ERR.
UNACKNOWLEDGED 36.1 RW NA
0=Undefined
1=Acknowledged
2=Unacknowledged
ALARM_STATE 36.2 RO NA
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
TIME_STAMP 36.3 RO NA
SUBCODE 36.4 RO NA
VALUE 36.5 RO