Table B‐42. Arithmetic Function Block Parameter Definitions
Label
PARAMETER_NAME
Index
Number
RO /
RW
Block
Mode
Range Initial Value Description
Static Revision
ST_REV
1 RO NA 0 to 65535 0
Data Type: Unsigned16
The revision level of the static data associated
with the function block. The revision value will
be incremented each time a static parameter
value in the block is changed.
Tag Description
TAG_DESC
2 RW ALL 7 bit ASCII Spaces
Data Type: Octet String
The user description of the intended
application of the block.
Strategy
STRATEGY
3 RW ALL 0 to 65535 0
Data Type: Unsigned16
The strategy field can be used to identify
grouping of blocks. This data is not checked or
processed by the block.
Alert Key
ALERT_KEY
4 RW ALL 1 to 255 0
Data Type: Unsigned8
The identification number of the plant unit.
This information may be used in the host for
sorting alarms, etc.
Block Mode
MODE_BLK
5
Data Type: DS‐69
Valid Bits: 7:OOS, 4:MAN, 3:AUTO
The actual, target, permitted, and normal
modes of the block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target
TARGET 5.1 RW ALL
OOS
MAN
AUTO
OOS until
block is
configured,
then last valid
target
ACTUAL 5.2 RO ALL OOS
PERMITTED 5.3 RW ALL OOS+MAN+AUTO
OOS+MAN+A
UTO
NORMAL 5.4 RO ALL AUTO
Block Error
BLOCK_ERR
6 RO NA
Defined Bits
1: Block Configuration
Error
3: Simulate Active
7: Input Failure / Bad PV
Status
14: Power‐up
15: Out‐of‐Service
Dynamic
Data Type: Bit String
0=Inactive
1=Active
The summary of all configuration or system
errors associated with the block.
Process Value
PV
7 RO NA
The process variable used in block execution
and alarm limit execution.
Output
OUT
8
OOS
MAN
The analog output value and status. The
number of outputs is an extensible parameter
in some blocks.
PRE_OUT
9 The pre‐trip limit from SP or zero.
Process Value Scale
PV_SCALE
10
The high and low scale values, engineering
units code, and number of digits to the right of
the decimal point associated with OUT.
Output Range
OUT_RANGE
11 ALL 0
Data Type: Unsigned16
Range of the output.
Grant Deny
GRANT_DENY
12
Data Type: DS‐70
Options for controlling access of host
computers and local control panels to
operating, tuning, and alarm parameters of
the block.
GRANT: 0=NA, 1=granted
DENY: 0=NA, 1=denied
GRANT 12.1 ALL
0: Program
1: Tune
2: Alarm
3: Local
All bits:0
DENY 12.2 ALL All bits: 0
Input Options
IO_OPTS
13
Sets the options for using IN, IN_LO, IN_1,
IN_2, and IN_3 when any are either Bad or
Uncertain.
Input
IN
14 ALL
Status
BAD:
NC:
const
Data Type: DS‐65
The analog input value and status. The
number of inputs is an extensible parameter in
some function blocks.
Value 0