Instruction Manual
Instruction Manual
D103434X012
Blocks
November 2014
135
Table B‐34. Input Selector Function Block Parameter Definitions (Continued)
Description
Initial
Value
Range
Block
Mode
RO / RW
Index
Number
Label
PARAMETER_NAME
Disable Analog Input 2
DISABLE_2
16 ALL
Status
BAD
NC
constant
Data Type: DS‐66
Enable/Disable for Input_2, If parameter is TRUE then
input is disabled. If parameter status is BAD it is not
evaluated.
Value
0=Use
1=Disable
0
Disable Analog Input 3
DISABLE_3
17 ALL
Status
BAD
NC
constant
Data Type: DS‐66
Enable/Disable for Input_3, If parameter is TRUE then
input is disabled. If parameter status is BAD it is not
evaluated.
Value
0=Use
1=Disable
0
Disable Analog Input 4
DISABLE_4
18 ALL
Status
BAD
NC
constant
Data Type: DS‐66
Enable/Disable for Input_4, If parameter is TRUE then
input is disabled. If parameter status is BAD it is not
evaluated.
Value
0=Use
1=Disable
0
Select Type
SELECT_TYPE
19 ALL
1=First Good
2=Minimum
3=Maximum
4=Middle
5=Average
6=Hot Spare
0
Data Type: Unsigned8
Determines the selector action
Min Good
MIN_GOOD
20 ALL
1 ‐ 4
0 initial value only
0
Data Type: Unsigned8
The minimum number of inputs which are “good” is
less than the value of MIN_GOOD then set the OUT
status to “bad”.
Selected
SELECTED
21 RO NA
Status
Data Type: DS‐66
The integer indicating the selected input number.
Value
0 ‐ 8
Dynamic
Operator Select
OP_SELECT
22 ALL
Status
BAD
NC
constant
Data Type: DS‐66
An operator settable parameter to force a given input
to be used.
Value
0 ‐ 8
0
Update Event
UPDATE_EVT
23
Data Type: DS‐73
This alert is generated by any change to the static data.
UNACKNOWLEDGED 23.1 RW NA
0=Undefined
1=Acknowledged
2=Unacknowledged
0
UPDATE_STATE 23.2 RO NA
0=Undefined
1=Update Reported
2=Updated not
reported
0
TIME_STAMP 23.3 RO NA 0
STATIC_REVISION 23.4 RO NA 0
RELATIVE_INDEX 23.5 RO NA 0
-Continued-