Blocks
November 2014
122
Table B‐27. Analog Output Function Block Parameter Definitions (Continued)
DescriptionInitial ValueRange
Block
Mode
RO /
RW
Index
Number
Label
PARAMETER_NAME
Setpoint Rate Down
SP_RATE_DN
18 ALL
Positive, 0 disables
rate limiting PV units
+INF
Data Type: Float
Ramp rate for downward set point changes. When
the ramp rate is set to zero, the set point is used
immediately.
Setpoint Rate Up
SP_RATE_UP
19 ALL
Positive, 0 disables
rate limiting PV units
+INF
Data Type: Float
Ramp rate for upward set point changes. When the
ramp rate is set to zero, the setpoint is used
immediately.
Setpoint High Limit
SP_HI_LIM
20 ALL PV Scale +/‐ 10% 100
Data Type: Float
The highest set point value allowed. SP_HI_LIM
must be greater than SP_LO_LIM.
Setpoint Low Limit
SP_LO_LIM
21 ALL PV Scale +/‐ 10% 0
Data Type: Float
The lowest set point value allowed. SP_LO_LIM
must be less than SP_HI_LIM.
AO Channel
CHANNEL
22 OOS
2:Temperature
3:Pressure
4:Upper Fluid Density
5:Lower Fluid Density
0
Data Type: Unsigned16
Defines which transducer parameter receives the
AO output.
Fault State Time
FSTATE_TIME
23 ALL Positive, seconds 0
Data Type: Float
Time from failure detection to reaction if failure still
exists.
Fault State Value
FSTATE_VAL
24 ALL PV Scale +/‐ 10% 0
Data Type: Float
Preset value to use if I/O_OPTS Fault State to Value
or Use Fault State Value on Restart is set.
Back Calculation Output
BKCAL_OUT
25 RO NA
Status Limits
Dynamic
Data Type: DS‐65
The value and status required by the BKCAL_IN
input of another block to prevent reset windup and
to provide bumpless transfer to closed loop
control.
Value
Remote Cascade Input
RCAS_IN
26 ALL
Status
BAD: NoCom:
NoVal:
const
Data Type: DS‐65
Target SP and status by supervisory host
Value 0 Trk
Shed Options
SHED_OPT
27 ALL
Defined by FF spec
0=Invalid
1=Normal Shed,
Normal Return
2=Normal Shed, No
Return
3=Shed to Auto,
normal return
4=Shed to Auto, no
return. Target mode
changes to Auto on
detection of a shed
condition
5=Shed to Manual,
normal return
6=Shed to Manual, No
return. Target mode
changes to MAN on
detection of a shed
condition.
7=Shed to retained
target, normal return
8=Shed to retained
target, no return.
(Change target to
retained target)
0
Data Type: Unsigned8
Defines the action to be taken when the set point is
not updated in a remote mode.
Remote Cascade Output
RCAS_OUT
28 RO NA
Status
Dynamic
Data Type: DS‐65
Block set point and status after ramping
Value
-Continued-