Instruction Manual DLC3020f Digital Level Controller D103434X012 Fisherr FIELDVUE™ DLC3020f Digital Level Controller for FOUNDATION™ fieldbus This manual applies to: 3020 Device Type 1 Device Revision Hardware Revision 1.0 Firmware Revision 1.0 DD Revision 0x03 www.Fisher.
Instruction Manual DLC3020f Digital Level Controller November 2014 D103434X012 Contents Section 5 Calibration . . . . . . . . . . . . . . . . . 41 Section 1 Introduction and Specifications . 3 Scope of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Instrument Description . . . . . . . . . . . . . . . . . . . . . . . . Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Instrument Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instruction Manual DLC3020f Digital Level Controller November 2014 D103434X012 Section 8 Parts . . . . . . . . . . . . . . . . . . . . . . 63 Parts Ordering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mounting Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Repair Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DLC3020f Digital Level Controllers . . . . . . . . .
Instruction Manual Introduction and Specifications D103434X012 November 2014 Section 1 Introduction and Specifications1‐1‐1 Scope of Manual This instruction manual includes specifications, installation, operating, and maintenance information for the FIELDVUE DLC3020f digital level controller. This manual describes device setup using AMS Suite: Intelligent Device Manager version 10.5 and later. You can also use the 475 or the 375 Field Communicator to setup the DLC3020f.
Introduction and Specifications November 2014 Instruction Manual D103434X012 D Resource Block—The resource block contains the hardware specific characteristics associated with a device; it has no input or output parameters. The resource block monitors and controls the general operation of other blocks within the device. For example, when the mode of the resource block is Out of Service, it impacts all function blocks.
Instruction Manual Introduction and Specifications D103434X012 November 2014 Specifications Specifications for DLC3020f are shown in table 1‐2. Specifications for 249 sensors are shown in table 1‐5. Related Information Fieldbus Installation and Wiring Guidelines This manual describes how to connect the fieldbus to the digital level controller.
Instruction Manual Introduction and Specifications November 2014 D103434X012 Table 1‐2. Specifications Available Configurations Block Execution Times AI, PID, DI, AO, ISEL: 15 ms ARTH: 25 ms Mounts on 249 caged and cageless sensors.
Instruction Manual Introduction and Specifications November 2014 D103434X012 Table 1‐2.
Instruction Manual Introduction and Specifications November 2014 D103434X012 Table 1‐3.
Instruction Manual Introduction and Specifications November 2014 D103434X012 Figure 1‐1. Style Number of Equalizing Connections STYLE 1 TOP AND BOTTOM CONNECTIONS SCREWED (S‐1) OR FLANGED (F‐1) STYLE 2 TOP AND LOWER SIDE CONNECTIONS SCREWED (S‐2) OR FLANGED (F‐2) STYLE 3 UPPER AND LOWER SIDE CONNECTIONS SCREWED (S‐3) OR FLANGED (F‐3) STYLE 4 UPPER SIDE AND BOTTOM CONNECTIONS SCREWED (S‐4) OR FLANGED (F‐4) 28B5536‐1 B1820‐2 Table 1‐6.
Instruction Manual Introduction and Specifications November 2014 D103434X012 Table 1‐7.
Instruction Manual Installation November 2014 D103434X012 Section 2 Installation2‐2‐ This section contains digital level controller installation information including an installation flowchart (figure 2‐1), mounting and electrical installation information. Figure 2‐1.
Installation November 2014 Instruction Manual D103434X012 Protecting the Coupling and Flexures CAUTION Damage to flexures and other parts can cause measurement errors. Observe the following steps before moving the sensor and controller. Lever Lock The lever lock is built in to the coupling access handle. When the handle is open, it positions the lever in the neutral travel position for coupling. In some cases, this function is used to protect the lever assembly from violent motion during shipment.
Instruction Manual Installation November 2014 D103434X012 Figure 2‐2.
Instruction Manual Installation November 2014 Figure 2‐3. Typical Caged Sensor Mounting D103434X012 Figure 2‐4. Typical Cageless Sensor Mounting A3788‐1 A3789‐1 The DLC3020f digital level controller is typically shipped attached to the sensor. If ordered separately, it may be convenient to mount the digital level controller to the sensor and perform the initial setup and calibration before installing the sensor on the vessel.
Instruction Manual Installation November 2014 D103434X012 manual). Changing the mounting also changes the effective action, because the torque tube rotation for increasing level, (looking at the protruding shaft), is clockwise when the unit is mounted to the right of the displacer and counter‐ clockwise when the unit is mounted to the left of the displacer. All 249 caged sensors have a rotatable head.
Instruction Manual Installation November 2014 D103434X012 Figure 2‐6. Close‐up of Set‐Screw SET‐SCREW (2mm) 2. Using a 10 mm deep well socket inserted through the access hole, loosen the shaft clamp (figure 2‐2). 3. Remove the hex nuts from the mounting studs. Do not remove the adapter ring. CAUTION Measurement errors can occur if the torque tube assembly is bent or misaligned during installation. 4. Position the digital level controller so the access hole is on the bottom of the instrument. 5.
Instruction Manual Installation November 2014 D103434X012 Figure 2‐8.
Installation November 2014 Instruction Manual D103434X012 WARNING Select wiring and/or cable glands that are rated for the environment of use (such as hazardous area, ingress protection and temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage from fire or explosion. Wiring connections must be in accordance with local, regional, and national codes for any given hazardous area approval.
Instruction Manual Installation November 2014 D103434X012 Figure 2‐9. Terminal Box Assembly CLIP‐ON + CLIP‐ON - RTD SIMULATE ENABLE SAFETY GROUND LOOP+ LOOP- Communication Connections WARNING Personal injury or property damage caused by fire or explosion may occur if this connection is attempted in a potentially explosive atmosphere or in an area that has been classified as hazardous.
Installation November 2014 Instruction Manual D103434X012 Install a jumper across the SIMULATE ENABLE terminals to enable the instrument to accept a simulate command. (These terminals are marked SIM + / - in the terminal box, as shown in figure 2‐9). With the jumper in place and the simulate software parameter set to enabled, various alerts can be simulated as required. Note Removing the jumper will disable the simulate, which may change the status of PV.
Instruction Manual Overview November 2014 D103434X012 Section 3 Overview3‐3‐ Overview AMS Device Manager Overview > Overview Field Communicator Overview > Overview Select the Overview tab (figure 3‐1) to access Overview and Shortcuts. Figure 3‐1.
Overview Instruction Manual November 2014 D103434X012 Advisory a configured advisory alert is active and configured failed or a maintenance alert is turned on Mode In Service the instrument is in service Not in Service the instrument is not in service Primary Purpose Variables Depending on your application, the primary purpose variables found on Overview may include the following: Fluid (Fluid for Level measurement, Upper Fluid and Lower Fluid or Interface measurement, when enabled).
Instruction Manual D103434X012 Overview November 2014 Manufacturing Identification Each instrument has a unique Device Identifier. The device identification provides in depth manufacturing data to help ensure reliability. D Lever Assembly ID D Communication Module ID D Sensor Module ID D Shop Order Number D Terminal Box Date Code Calibration/Setup Logs Logs including calibration, instrument setup, and process fluid data can be saved for future reference or re‐use. The instrument can store up to 30 logs.
Overview November 2014 24 Instruction Manual D103434X012
Instruction Manual Configuration November 2014 D103434X012 Section 4 Configuration4‐4‐ Note The primary transducer block must be set to out of service before the device can be configured. When using AMS Device Manager 10.1 and earlier go to Target Mode in Block Modes tab to set the primary transducer block in and out of service. Refer to figure 4‐1. Figure 4‐1. Block Modes Tab (AMS Device Manager 10.
Instruction Manual Configuration November 2014 D103434X012 Figure 4‐2. Guided Setup INSTRUMENT SETUP GUIDED SETUP CONFIGURE Manual Setup AMS Device Manager Configure > Manual Setup Field Communicator Configure > Manual Setup The Device, Process Fluid, Instrument Display, Snap Acting Control, and Options tabs are accessible through Manual Setup.
Instruction Manual Configuration November 2014 D103434X012 Device Select the Device tab (figure 4‐3) to access Variable Configuration, Sensor Limits, Sensor Hardware Information, Sensor Units, Mode, Sensor Parameters, Instrument Mount Position, and Torque Tube. Figure 4‐3.
Instruction Manual Configuration November 2014 D103434X012 The Upper and Lower Sensor Limit limit what the DLC3020ft can read; values above and below these limits will not be detected by the instrument. This is a dynamic reading based on temperature used when Temperature Compensation is enabled. Sensor Hardware Information Enter the following information by selecting Sensor Hardware Information.
Instruction Manual Configuration November 2014 D103434X012 Volume Units—mm3, ml, L, in3 Weight Units—oz, lb, g, or kg Temperature Units—_F, _R, _C, or K Torque Rate Units—NSm/deg, dyneScm/deg, lbfSin/deg Fluid Density Units—degAPI, SGU (Specific Gravity) lb/in3, lb/ft3, lb/gal, degBaum hv, degBaum lt, kg/m3, g/cm3, kg/L, g/ml, or g/L Sensor Parameters Enter the sensor parameters. Selections shown in the drop down are based on the sensor units chosen.
Instruction Manual Configuration November 2014 D103434X012 Figure 4‐5. Method of Determining Driver Rod Length from External Measurements VERTICAL CL OF DISPLACER VESSEL HORIZONTAL CL OF TORQUE TUBE DISPLACER ROD LENGTH Torque Tube Torque Tube Material—select the material of the torque tube being used. See the sensor nameplate. View Torque Tube Table—select View Torque Tube Table to see the torque tube gain over the entire temperature range and the compensated torque rate.
Instruction Manual Configuration November 2014 D103434X012 Process Fluid Select the Process Fluid tab (figure 4‐6) to access Process Fluid, Temperature Compensation, and Mode. Figure 4‐6. Configure > Manual Setup > Process Fluid PROCESS FLUIDS TAB PROCESS FLUID TEMPERATURE COMPENSATION MODE MANUAL SETUP CONFIGURE CHANGE PROCESS FLUID VIEW DENSITY PARAMETERS Note The instrument software contains density tables for common categories of fluids. Custom tables can be built if needed.
Instruction Manual Configuration November 2014 D103434X012 Temperature Input—select None, Manual, AO Block, or RTD. Temperature compensation, when enabled, can come from a manually entered temperature, a temperature from a fieldbus transmitter (AO block) or a temperature from an RTD. Temperature for Compensation—the temperature in use for fluid density and torque tube material compensation.
Instruction Manual Configuration November 2014 D103434X012 Display Primary Value Offset Enter the PV Offset to apply it to the LCD readout. Scrolling Message Control Messages that can be scrolled on the LCD screen. Choose from; Primary Value Bad, Primary Value Uncertain, Failed Alert, Maintenance Alert, or Advisory Alert.
Configuration Instruction Manual November 2014 D103434X012 Primary Value Percent PV in % DI1 Trip Point Settings Set Channel 1 or 2 of the DI for snap acting control. DI1 Action—indicate whether the trip point is active on rising or falling level. DI1 Trip Point—enter the point where DI1 is active. DI1 Deadband—enter the desired deadband. This is the distance away from the trip point that DI1 clears. DI1 Readback—indicates the status of the trip point. 0 indicates that DI1 Trip is inactive.
Instruction Manual Configuration November 2014 D103434X012 Figure 4‐9. Configure > Manual Setup > Options COMMUNICATION TIMEOUT MANUAL SETUP CONFIRM TIME WRITE ALARM OPTIONS TAB MODE FUNCTION BLOCK AVAILABLE ALERT KEY MAXIMUM ALERTS ALLOWED MAXIMUM ALERTS POSSIBLE BOCK ALARM RESOURCE BLOCK TRANSDUCER BLOCK CONFIGURE WRITE LOCK FEATURES SELECTED Write Alarm The Write Alarm (WRITE_ALM [40]) is used to alert when parameters are writable to the device.
Configuration Instruction Manual November 2014 D103434X012 Write Lock— When Write Lock is set to Locked, no writes are permitted to any parameters within the device except to set Write Lock to Not Locked. When locked, the device functions normally, updating inputs and outputs and executing algorithms. When Write Lock is set to Not Locked, the Write Alarm alert is active. Write Priority—Write Priority sets the priority for Write Alarm. The lowest priority is 0. The highest is 15.
Instruction Manual D103434X012 Configuration November 2014 Features Selected Note Typically this parameter does not need to be changed. The unit will be operational using the default values assigned by the factory. Features Selected indicates which Resource Block Options features have been selected and is used to select the desired features. Reports—Selecting reports enables alert and event reporting. Reporting of specific alerts may be suppressed.
Instruction Manual Configuration November 2014 D103434X012 Alert Setup AMS Device Manager Configure > Alert Setup Field Communicator Configure > Alert Setup Alert Setup is accessible through the Alert Setup tab (figure 4‐10). Figure 4‐10. Alert Setup ALERT SETUP ALERT SETUP TAB ELECTRONICS OPERATIONAL RATE LIMIT CONFIGURE SCROLL DOWN TO VIEW: SENSOR BOARD TEMPERATURE LIMIT INPUT COMPENSATION ERROR Alerts The DLC3020f provides two levels of alerts; Instrument alerts and PlantWeb alerts.
Instruction Manual Configuration D103434X012 November 2014 PlantWeb Alerts Instrument alert conditions can be used to trigger PlantWeb alerts that will be reported in Failed, Maintenance or Advisory categories, as configured by the user. PlantWeb alerts, when enabled, can participate in the DeltaVt alarm interface tools such as the alarm banner, alarm list and alarm summary.
Configuration November 2014 Instruction Manual D103434X012 RTD Sensor D RTD Sensor—when selected indicates if the RTD readings are out of range or the RTD is incorrectly connected. D RTD Open—when selected indicates if the RTD is not connected. Sensor Board D Instrument Temperature Sensor— when selected indicates if the electronic sensor readings are out of range.
Instruction Manual Calibration November 2014 D103434X012 Section 5 Calibration5‐5‐ Calibrate Guided Calibrations AMS Device Manager Configure > Calibrate > Guided Calibrations Field Communicator Configure > Calibrate > Full Calibration (Bench) or Full Calibration (Field) Guided Calibrations (figure 5‐1) provides access to guided calibration methods for use in the field or on the bench. Figure 5‐1.
Instruction Manual Calibration November 2014 D103434X012 Calibrate Instrument Choose Full Calibration (Bench) or Full Calibration (Field) and follow AMS Device Manager (or the Field Communicator or other host system) prompts to calibrate the instrument. Guided Calibration recommends an appropriate calibration procedure.
Instruction Manual D103434X012 Calibration November 2014 Calibrator—indicates who performed the calibration. Calibration Method—indicates the method of calibration. Calibration Descriptions Full Calibration Weight (Bench only)—Weight Calibration is a bench calibration where weights are used to simulate the different forces the device sees at the minimum and maximum levels. All configuration data is needed to perform a Weight calibration.
Calibration November 2014 Instruction Manual D103434X012 Trim Current Calibration Zero Trim—Zero trim is an adjustment to the current calibration. This adjustment assumes that the current torque rate is correct and the PV error is due to a shift in the zero position. Gain Trim—Gain trim is an adjustment to the current calibration. This adjustment assumes that the zero point is correct and the PV error is caused by a torque rate change. Default Gain—Default Gain is an adjustment to the current calibration.
Instruction Manual Service Tools November 2014 D103434X012 Section 6 Service Tools6‐6‐ Service Tools Alerts AMS Device Manager Service Tools > Alerts Field Communicator Service Tools > Alerts Active alerts are displayed on the Active Alerts tab (figure 6‐1). Figure 6‐1. Service Tools > Alerts ACTIVE ALERTS TAB ALERTS SERVICE TOOLS Alert Conditions The alert conditions for each group of alerts are listed below.
Instruction Manual Service Tools November 2014 D103434X012 D PV Range Exceeds Sensor Range— active if the Primary Variable (PV) Range has exceeded the range of the sensor's current calibration. The PV is still accurate but could move out of sensor range. D PV Exceeds Primary Range— active if the The Primary Variable (PV) has exceeded the PV Range. D Calibration Validity— active if a vital calibration parameter has been changed.
Instruction Manual Service Tools November 2014 D103434X012 Figure 6‐2.
Instruction Manual Service Tools November 2014 D103434X012 D Time Since Reset D Temperature Limit Instrument Temperature D Upper Temperature Limit Maximum Recorded Temperature Time Over Upper Temperature Limit D Lower Temperature Limit Minimum Recorded Temperature Time Under Lower Temperature Limit D Temperature Integral Simulate AMS Device Manager Service Tools > Simulate Field Communicator Service Tools > Simulate Simulate (as shown in figure 6‐3) is used to validate that user‐configured alerts ca
Instruction Manual Service Tools November 2014 D103434X012 Maintenance AMS Device Manager Service Tools > Maintenance Field Communicator Service Tools > Maintenance Calibration Setup/Logs, Instrument Display Test, and Restart Device are accessible through the Maintenance tab (figure 6‐4). Figure 6‐4.
Instruction Manual Service Tools November 2014 D103434X012 Restore—select Restore to access stored logs; select the desired log to revert back to. Save Current—select Save Current and enter a new name. Rename—select Rename to change the name of an existing log. Delete—select Delete to delete to delete an existing log. D Mode—indicates whether the instrument is In Service or Not In Service.
Instruction Manual Maintenance & Troubleshooting D103434X012 November 2014 Section 7 Maintenance & Troubleshooting7‐7‐ The DLC3020f digital level controller features modular design for easy maintenance. If you suspect a malfunction, check for an external cause before performing the diagnostics described in this section. Sensor parts are subject to normal wear and must be inspected and replaced as necessary. For sensor maintenance information, refer to the appropriate sensor instruction manual.
Instruction Manual Maintenance & Troubleshooting November 2014 D103434X012 Table 7‐1. Tools Required Tool Size Usage Keys Handle Cover‐lock set screws 31 20 Hex Key 2 mm Hex Key 2.
Instruction Manual Maintenance & Troubleshooting D103434X012 November 2014 7. When re‐installing the digital level controller, follow the appropriate procedure outlined in the Installation section. Also setup the digital level controller as described in the Initial Setup section. 249 Sensor in High Temperature Application 1. Loosen the set screw (key 31) in the terminal box cover assembly (key 6) so that the cover can be unscrewed from the terminal box. 2.
Instruction Manual Maintenance & Troubleshooting November 2014 D103434X012 The digital level controller is designed with a dual‐compartment housing; one compartment contains the LCD meter and Electronics Module; the other contains all wiring terminals and the communication receptacles. The LCD meter is located in the compartment opposite the wiring terminals, as shown in figure 7‐1. Figure 7‐1.
Instruction Manual D103434X012 Maintenance & Troubleshooting November 2014 3. Attach the meter to the interconnection pins. Thread the long meter screws into the holes on the Electronics Module and tighten to secure the meter. 4. Note the position of the alarm jumper on the LCD meter removed from the digital level controller. Remove the alarm jumper and install it on the replacement meter in the same position. 5. Install the six‐pin dual header on the LCD meter.
Maintenance & Troubleshooting November 2014 Instruction Manual D103434X012 CAUTION To prevent damage to the interconnecting pins when installing the Electronics Module, use the guide pins to insert the Electronics Module straight onto the Transducer housing receptacles without twisting or turning. 2. Tighten the two mounting screws. Replace the LCD meter assembly. 3. Replace the cover. Tighten 1/3 of a revolution after the cover begins to compress the O‐ring.
Instruction Manual Maintenance & Troubleshooting D103434X012 November 2014 CAUTION To avoid damaging the mating pins in the transducer housing, ensure that the guiding mechanism is engaged properly before applying force. 3. Fasten the terminal box to the transducer housing with the screw (key 7). Tighten the screw to 6 NSm (53 lbfSin). 4. Apply sealant to the O‐ring (key 26) and install the O‐ring over the cover threads on the terminal box.
Instruction Manual Maintenance & Troubleshooting November 2014 D103434X012 Figure 7‐2. Installing Inner Guide and Access Handle Assembly SCREWS (KEY 13) HANDLE ASSEMBLY (KEY 12) VENT HOLES LUBRICATE THIS SURFACE LUBRICATE THIS SURFACE VENT HOLE TRANSDUCER HOUSING INNER GUIDE (KEY 11) ZERO LOCKING PIN ACCESS HOLE E0381 6.
Instruction Manual Maintenance & Troubleshooting D103434X012 November 2014 3. Remove the coupling shield (key 16) by removing the two screws (key 13). Take care not to drop the screws into the lever assembly compartment where they will be attracted by the magnets. 4. Inspect the lever assembly alignment with the housing. If it is off center or not co‐axial with the main housing, continue with the removal procedure. 5. Loosen and remove the mounting screw (key 14) from the lever assembly. 6.
Instruction Manual Maintenance & Troubleshooting November 2014 D103434X012 Instrument Troubleshooting If communication or output difficulties are experienced with the instrument, refer to the troubleshooting information provided in 7‐2. Table 7‐2. Troubleshooting Symptom Possible Cause 1. Output Drifting while at fixed process 1.a Sensor input. 1.b Configuration Data 2. Instrument will not communicate. 2.a No power to device 2.c Incompatible network settings 2.d Defective terminal box. 3.
Instruction Manual Maintenance & Troubleshooting November 2014 D103434X012 Table 7‐2. Troubleshooting Symptom 5. Function block actual mode does not change with target mode. Possible Cause 5.a Resource block actual mode is Out of Service. 5.b Transducer block actual mode is not Auto. 5.c Schedules that define when function blocks execute are not set correctly. 5.d Configuration error 6. Input or Output Block does not go to mode target 6.a Resource block actual mode is Out of Service 6.
Maintenance & Troubleshooting November 2014 62 Instruction Manual D103434X012
Instruction Manual D103434X012 Parts November 2014 Section 8 Parts8‐8‐ Parts Ordering Whenever corresponding with your Emerson Process Management sales office about this equipment, always mention the controller serial number. When ordering replacement parts, refer to the 11‐character part number of each required part as found in the following parts list. Parts that do not show part numbers are not orderable. WARNING Use only genuine Fisher replacement parts.
Instruction Manual Parts November 2014 D103434X012 Parts Kits Description 1* Small Hardware Spare Parts Kit Includes Screw (key 7) Screw, hex socket (key 13) Screw, cap, hex socket (key 14) Set Screw (key 20) Set Screw (key 31) Test Terminal (key 24) Wire Retainer (key 25) Nut (key 34) Alarm Jumper (key 35) (not used for DLC3020f) Header Assembly (key 38) Part Number 19B1643X052 Qty/kit 1 6 1 2 2 4 8 4 2 2 2* Spare O‐Rings Kit Includes three each of keys 21, 26, and 27 19B1643X022 3* Coupling H
Instruction Manual Parts November 2014 D103434X012 Figure 8‐1.
Instruction Manual Parts November 2014 D103434X012 Transducer Assembly (figure 8‐2) Key Description 10 11 12 Transducer Housing Inner Guide, aluminum Handle Assembly, aluminum/SST 13 14 15 Screw, hex socket, 18‐8 SST (4 req'd) Screw, cap, 18‐8 SST Lever Assembly, aluminum/SST/NdFeB 16 17 Coupling Shield, 18‐8 SST Align/Clamp Ring Key Description 19 20 67 68 76 Machine Screw, pan head (2 req'd) Set Screw, 18‐8 SST(2) Thread Locking adhesive (medium strength) (not furnished with instrument) Seal
Instruction Manual Parts November 2014 D103434X012 Terminal Box Assembly (figure 8‐3) Key Description O‐Ring, nitrile(3) O‐Ring, nitrile(3) Pipe Plug, 18‐8 SST Sealant, Silicone (not furnished with instrument) Anti‐Seize Compound (not furnished with instrument) Key Description 26* 27* 28 23 25 Terminal Box Subassembly Wire Retainer, 18‐8 SST (8 req'd)(2) 65 66 Part Number 1H8762X0012 10A8218X032 Figure 8‐3. Terminal Box Assembly A APPLY LUBRICANT GE29688 Figure 8‐4.
Instruction Manual Parts November 2014 D103434X012 Mounting Parts These parts are available as a kit as indicated in the Mounting Kits section. Contact your Emerson Process Management sales office for ordering information.
Instruction Manual D103434X012 Parts November 2014 Figure 8‐6. Mounting Kit for Masoneilan 12200 and 12300 Sensor without Heat Insulator 29B8444‐A Figure 8‐7.
Instruction Manual Parts November 2014 Yamatake NQP Sensor Key Description D103434X012 Foxboro‐Eckardt Sensors Key Description 144LD without Heat Insulator Without Heat Insulator 58 59 60 62 63 71 72 73 Shaft Extension, S31600 Shaft Retainer, S30400 Hex Socket Screw, SST Mounting Adaptor, A96061 Hex Socket Screw, SST (3 req'd) Hex Socket Screw, SST (3 req'd) Shaft Adapter, S30400 Hex Socket Screw, SST (2 req'd) With Heat Insulator 57 58 59 60 61 62 63 71 72 73 78 70 Heat Insulator, S30400 Shaft E
Instruction Manual Principle of Operation November 2014 D103434X012 Appendix A Principle of Operation1‐1‐ Digital Level Controller Operation The DLC3020f digital level controller is a fieldbus‐powered instrument that measures liquid level or interface between two liquids. As the liquid level surrounding the displacer rises (figure A‐1), the torque tube rotates clockwise; the reverse action occurs when the liquid level is lowered.
Instruction Manual Principle of Operation November 2014 D103434X012 Figure A‐2.
Instruction Manual Blocks November 2014 D103434X012 Appendix B BlocksB‐ Analog Input (AI) Function Block The Analog Input (AI) function block (figure B‐1) processes field device measurements and makes them available to other function blocks. The output value from the AI block is in engineering units and contains a status indicating the quality of the measurement. The measuring device reports level status. OUT_D OUT FIELDBUS‐FBUS_31A Figure B‐1.
Instruction Manual Blocks November 2014 D103434X012 Figure B‐2. Analog Input Function Block Schematic ANALOG MEASUREMENT ALARM_TYPE ACCESS ANALOG MEAS. HI_HI_LIM HI_LIM LO_LO_LIM LO_LIM CHANNEL ALARM DETECTION OUT_D ALARM_HYS LOW_CUT SIMULATE L_TYPE FIELD_VAL PV PV_FTIME IO_OPTS STATUS CALC. OUT FIELDBUS‐FBUS_02A CUTOFF FILTER CONVERT MODE STATUS_OPTS OUT_SCALE XD_SCALE NOTES: OUT_D = BLOCK OUTPUT VALUE AND STATUS OUT_D = DISCRETE OUTPUT THAT SIGNALS A SELECTED ALARM CONDITION.
Instruction Manual Blocks November 2014 D103434X012 Figure B‐3. Analog Input Function Block Timing Diagram OUT (mode in man) OUT (mode in auto) PV FIELD_VAL TIME (seconds) PV_FTIME FIELDBUS‐FBUS_03A 63% of Change Status Handling The AI block only gets Good Non‐Specified Unlimited or Bad Device Failure for status from the transducer. This is reflected in FIELD_VAL.STATUS [19.1]. PV.STATUS [7.1] is the same as FIELD_VAL.STATUS [19.1]. OUT.STATUS [8.
Instruction Manual Blocks November 2014 D103434X012 Signal Conversion You can set the signal conversion type with the Linearization Type (L_TYPE [16]) parameter. You can view the converted signal (in percent of XD_SCALE [10]) through the FIELD_VAL [19] parameter. FIELD_VAL = 100 X (Channel Value) ‐ EU *@0% (EU *@100% ‐ EU *@0%) *XD_SCALE values You can choose from direct, indirect, or indirect square root signal conversion with the L_TYPE [16] parameter.
Instruction Manual Blocks November 2014 D103434X012 Advanced Features The AI function block provided with the DLC3020f provides added capability through the addition of the following parameters: ALARM_SEL—Allows one or more of the process alarm conditions detected by the AI function block to be used in setting its OUT_D [37] parameter. OUT_D—Discrete output of the AI function block based on the detection of process alarm condition(s).
Instruction Manual Blocks November 2014 D103434X012 Troubleshooting Refer to table B‐4 to troubleshoot any problem that you encounter. Table B‐4. Troubleshooting Symptom Mode will not leave OOS Possible Causes Target mode is not set Configuration error Corrective Action Set target mode to something other than OOS BLOCK_ERR [6] will show the configuration error bit set.
Instruction Manual Blocks November 2014 D103434X012 AI Block Parameter List D Read/Write Capability: RO ‐ Read Only, RW ‐ Read Write D Mode: The block mode(s) required to write to the parameter D Double indentation and shaded Index Number indicates sub‐parameter Table B‐5.
Instruction Manual Blocks November 2014 D103434X012 Table B‐5. Analog Input Block Parameter Definitions (Continued) Label PARAMETER_NAME Simulate SIMULATE Index Number RO / RW Write Block Mode Range 9.1 ALL 0 SIMULATE_VALUE 9.2 ALL 0 TRANSDUCER_STATUS 9.3 RO TRANSDUCER_VALUE 9.4 RO Transducer Scale XD_SCALE 9.
Instruction Manual Blocks November 2014 D103434X012 Table B‐5. Analog Input Block Parameter Definitions (Continued) Label PARAMETER_NAME Updated Event UPDATE_EVT UNACKNOWLEDGED Index Number RO / RW Write Block Mode RW NA 0=Undefined 1=Acknowledged 2=Unacknowledged 0=Undefined 0=Undefined 1=Update reported 2=Update not reported 0=Undefined Range Initial Value 20 20.1 UPDATE_STATE 20.2 RO NA TIME_STAMP 20.3 RO NA 0 STATIC_REVISION 20.4 RO NA 0 RELATIVE_INDEX 20.
Instruction Manual Blocks November 2014 D103434X012 Table B‐5. Analog Input Block Parameter Definitions (Continued) Label PARAMETER_NAME High High Alarm HI_HI_ALM Index Number RO / RW Write Block Mode Range Initial Value 33 UNACKNOWLEDGED 33.1 RW 0 ALARM_STATE 33.2 RO 0 TIME_STAMP 33.3 RO SUBCODE 33.4 RO 0 VALUE 33.5 RO 0 High Alarm HI_ALM 0 NA 34.1 RW 0 ALARM_STATE 34.2 RO 0 TIME_STAMP 34.3 RO SUBCODE 34.4 RO 0 VALUE 34.
Instruction Manual Blocks November 2014 D103434X012 View Lists View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer. Table B‐6. AI Function Block, View 1 Index Number 1 Parameter Table B‐9.
Instruction Manual Blocks November 2014 D103434X012 Field Communicator Menu Structure ANALOG INPUT FUNCTION BLOCK Quick Config AI Channel Linearization Type Transducer Scale: EU at 100% Transducer Scale: EU at 0% Transducer Scale: Units Index Transducer Scale: Decimal Output Scale: EU at 100% Output Scale: EU at 0% Output Scale: Units Index Output Scale: Decimal Common Config Acknowledge Option Alarm Hysteresis Alert Key High High Limit High High Priority High Limit High Priority I/O Options Linearizati
Instruction Manual Blocks November 2014 D103434X012 PID Function Block The PID function block (figure B‐4) combines all of the necessary logic to perform proportional/integral/derivative (PID) control. The block supports mode control, signal scaling and limiting, feedforward control, override tracking, alarm limit detection, and signal status propagation. Figure B‐4.
Instruction Manual Blocks November 2014 D103434X012 parameters and their descriptions, units of measure, and index numbers, and figure B‐5 illustrates the internal components of the PID function block. Figure B‐5.
Instruction Manual D103434X012 Blocks November 2014 D RemoteOutput (ROut)—The OUT [9] is provided by a host computer that writes to the ROUT_IN [33] parameter. D Local Override (LO)—The track function is active. OUT [9] is set by TRK_VAL [39]. The BLOCK_ERR [6] parameter shows Local override. D Initialization Manual (IMan)—The output path is not complete (for example, the cascade‐to‐slave path might not be open). In IMan mode, OUT [9] tracks BKCAL_IN [27].
Instruction Manual Blocks November 2014 D103434X012 Man—On failure of a remote connection, the block sets the target mode to Man, if permitted. The user may configure SHED_OPTS [34] so that it calls for a target mode that is not permitted. When doing this, the mode logic uses the following rules as applied by the remote logic: D Shed logic never results in a non‐permitted target mode. D Shed logic never attempts to attain an actual mode of Auto or Cas if that mode is not permitted.
Instruction Manual D103434X012 Blocks November 2014 Feedforward Calculation The feedforward value (FF_VAL [40]) is scaled (FF_SCALE [41]) to a common range for compatibility with the output scale (OUT_SCALE [11]). A gain value (FF_GAIN [42]) is applied to achieve the total feedforward contribution. Output Tracking Output tracking is enabled through the control options. You can set control options in Manual or Out of Service mode only.
Blocks November 2014 Instruction Manual D103434X012 PID Equation Structures for Enhanced PID Block Note Extended parameters are not available at this time for all host systems. Refer to your host system documentation, or contact your Emerson Process Management sales office for additional information. Configure the STRUCTURECONFIG [71] parameter to select the PID equation structure.
Instruction Manual Blocks November 2014 D103434X012 In order to avoid alarm chattering when the variable is oscillating around the alarm limit, an alarm hysteresis in percent of the PV span can be set using the ALARM_HYS [47] parameter. The priority of each alarm is set in the following parameters: D HI_PRI [50] D HI_HI_PRI [48] D LO_PRI [52] D LO_LO_PRI [54] D DV_HI_PRI [56] D DV_LO_PRI [58] Alarms are grouped into five levels of priority, as shown in table B‐10. Table B‐10.
Instruction Manual Blocks November 2014 D103434X012 PID Block Parameter List D Read/Write Capability: RO ‐ Read Only, RW ‐ Read Write D Mode: The block mode(s) required to write to the parameter D Double indentation and shaded Index Number indicates sub‐parameter Table B‐12.
Instruction Manual Blocks November 2014 D103434X012 Table B‐12. PID Function Block System Parameters Definitions (Continued) Label PARAMETER_NAME Grant Deny GRANT_DENY Index Number RO / RW Block Mode Range Initial Value Description 12 Data Type: DS‐70 Options for controlling access of host computers and local control panels to operating, tuning, and alarm parameters of the block. Not used by the device. GRANT: 0=NA, 1=granted DENY: 0 = NA, 1= denied GRANT 12.
Instruction Manual Blocks November 2014 D103434X012 Table B‐12. PID Function Block System Parameters Definitions (Continued) Label PARAMETER_NAME Index Number RO / RW Block Mode Range Initial Value Description Balance Time BAL_TIME 25 ALL Positive 0 Data Type: Float The specified time, in seconds, for the internal working value of bias to return to the operator set bias.
Instruction Manual Blocks November 2014 D103434X012 Table B‐12.
Instruction Manual Blocks November 2014 D103434X012 Table B‐12. PID Function Block System Parameters Definitions (Continued) Label PARAMETER_NAME Alarm Summary ALARM_SUM Index Number RO / RW Block Mode Range Initial Value 45 CURRENT 45.1 RO ALL UNACKNOWLEDGED 45.2 RO ALL UNREPORTED 45.3 RO ALL DISABLED 45.
Instruction Manual Blocks November 2014 D103434X012 Table B‐12. PID Function Block System Parameters Definitions (Continued) Label PARAMETER_NAME VALUE High Alarm HI_ALM UNACKNOWLEDGED Index Number RO / RW Block Mode 60.5 RO NA RW NA 0=Undefined 1=Acknowledged 2=Unacknowledged 0=undefined 0=Undefined 1=Clear reported 2=Clear not reported 3=Active reported 4=Active not reported 0=undefined Range Initial Value 61 61.1 ALARM_STATE 61.2 RO NA TIME_STAMP 61.
Instruction Manual Blocks November 2014 D103434X012 Table B‐12. PID Function Block System Parameters Definitions (Continued) Label PARAMETER_NAME Deviation Low Alarm DV_LO_ALM UNACKNOWLEDGED Index Number RO / RW Block Mode RW NA 0=Undefined 1=Acknowledged 2=Unacknowledged 0=undefined 0=Undefined 1=Clear reported 2=Clear not reported 3=Active reported 4=Active not reported 0=undefined Range Initial Value Description 65 65.1 ALARM_STATE 65.2 RO NA TIME_STAMP 65.
Instruction Manual Blocks November 2014 D103434X012 Table B‐12. PID Function Block System Parameters Definitions (Continued) Label PARAMETER_NAME Index Number RO / RW Block Mode Range Initial Value Description Data Type: Float Integral action stops when ERROR is within IDEADBAND, proportional and derivative action continue. EU of PV_SCALE IDeadBand IDEADBAND 74 StdDev STDDEV 75 RO NA Dynamic Data Type: Float Standard deviation of PV.
Instruction Manual Blocks November 2014 D103434X012 View Lists View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer. Table B‐13. PID Function Block, View 1 Index Number 1 Parameter ST_REV 5.1 MODE_BLK.TARGET_MODE 5.
Instruction Manual Blocks November 2014 D103434X012 Note Because individual views are limited in size, View List 4 has two parts. Table B‐16. PID Function Block, View 4.
Instruction Manual Blocks November 2014 D103434X012 Field Communicator Menu Structure PID FUNCTION BLOCK Quick Config Alert Key Control Options Deviation High Limit Deviation Low Limit Gain High High Limit High Limit Low Limit Low Low Limit Output Scale: EU at 100% Output Scale: EU at 0% Output Scale: Units Index Output Scale: Decimal Process Value Scale: EU at 100% Process Value Scale: EU at 0% Process Value Scale: Units Index Process Value Scale: Decimal Reset Setpoint: Status Setpoint: Value Setpoint
Instruction Manual Blocks November 2014 D103434X012 PID FUNCTION BLOCK (continued) Other Tag Description Grant Deny: Grant Grant Deny: Deny Balance Time Update Event: Unacknowledged Update Event: Update State Update Event: Time Stamp Update Event: Static Rev Update Event: Relative Index Block Alarm: Unacknowledged Block Alarm: Alarm State Block Alarm: Time Stamp Block Alarm: Subcode Block Alarm: Value Alarm Summary: Current Alarm Summary: Unacknowledged Alarm Summary: Unreported Alarm Summary: Disabled Ac
Instruction Manual Blocks November 2014 D103434X012 Discrete Input (DI) Function Block The Discrete Input (DI) function block (figure B‐7) processes a single discrete input from a field device and makes it available to other function blocks. You can configure inversion and alarm detection on the input value. In the DLC2030f, the discrete input function block can provide level switch functionality. The DI function block supports mode control, signal status propagation, and simulation. Figure B‐7.
Instruction Manual D103434X012 Blocks November 2014 Modes The Discrete Input function block supports the following modes: D Manual (Man)—The block output (OUT_D [8]) is disconnected from the field and set manually. D Automatic (Auto)—The block algorithm determines output. D Out of Service (OOS)—The block is not processed. The OUT_D [8] status is set to Bad: Out of Service. The BLOCK_ERR [6] parameter shows Out of Service.
Instruction Manual Blocks November 2014 D103434X012 Figure B‐9. Discrete Input Proximity Detection Function (Snap Acting Controller) DEPICTS RISING POINT ACTIVE DISCRETE INPUT CLEARED (RISING POINT) RISING DEADBAND LEVEL DEPICTS FALLING POINT ACTIVE FALLING DEADBAND DISCRETE INPUT SET (FALLING POINT) TIME DI Rising TIME DI Falling Table B‐18.
Instruction Manual Blocks November 2014 D103434X012 Block Errors Table B‐19 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the DI block and are provided only for your reference. Table B‐19. BLOCK_ERR Conditions Condition Number Condition Name and Description 0 Other (NA) 1 Block Configuration Error—CHANNEL set to 0 through 10 (uninitialized) 2 Link Configuration Error (NA) 3 Simulate Active—Simulate is enabled.
Instruction Manual Blocks November 2014 D103434X012 Discrete Input Function Block Parameter List D Read/Write Capability: RO ‐ Read Only, RW ‐ Read Write D Mode: The block mode(s) required to write to the parameter D Double indentation and shaded Index Number indicates sub‐parameter Table B‐20.
Instruction Manual Blocks November 2014 D103434X012 Table B‐20. Discrete Input Function Block Parameter Definitions (Continued) Label PARAMETER_NAME Simulate Discrete SIMULATE_D Index Number RO / RW Block Mode Range Initial Value Description Data Type: DS‐83 Allows the transducer discrete input or output to the block to be manually supplied when simulate is enabled. When simulation is disabled, the simulate value and status track the actual value and status. 9 SIMULATE_STATUS 9.
Instruction Manual Blocks November 2014 D103434X012 Table B‐20. Discrete Input Function Block Parameter Definitions (Continued) Label PARAMETER_NAME Block Alarm BLOCK_ALM UNACKNOWLEDGED Index Number RO / RW Block Mode 19 19.1 Initial Value Description Dynamic RW NA 0=Undefined 1=Acknowledged 2=Unacknowledged 0=Undefined 1=Clear reported 2=Clear not reported 3=Active reported 4=Active not reported ALARM_STATE 19.2 RO NA TIME_STAMP 19.3 RO NA SUBCODE 19.4 RO NA VALUE 19.
Instruction Manual Blocks November 2014 D103434X012 View Lists View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer. Table B‐21. DI Function Block, View 1 Index Number 1 Parameter ST_REV Table B‐23.
Instruction Manual Blocks November 2014 D103434X012 Field Communicator Menu Structure DISCRETE INPUT FUNCTION BLOCK Quick Config Alert Key Process Value Discrete: Status Process Value Discrete: Value Common Config Alert Key Discrete Limit I/O Options Block Mode: Target Block Mode: Actual Block Mode: Permitted Block Mode: Normal Process Value Filter Time Advanced Config DI Channel Output State Simulate Discrete: Simulate Status Simulate Discrete: Simulate Value Simulate Discrete: Transducer Status Simula
Instruction Manual Blocks November 2014 D103434X012 Analog Output (AO) Function Block The Analog Output (AO) function block (figure B‐10) assigns an output value to a field device through a specified I/O channel. The block supports mode control, signal status calculation, and simulation. Figure B‐11 illustrates the internal components of the AO function block, and table B‐27 lists the definitions of the block parameters. Figure B‐10.
Instruction Manual Blocks November 2014 D103434X012 Figure B‐11.
Instruction Manual D103434X012 Blocks November 2014 When the block is in Cas mode and the CAS_IN [17] input goes bad, the block sheds mode to the next lower permitted mode. You can configure the shed option as follows: Shed With Return Options Remote cascade connection failure shifts actual mode but keeps trying to restore remote cascade (in other words, the remote cascade target mode stays in effect).
Blocks Instruction Manual November 2014 D103434X012 D Shed logic never results in a non‐permitted target mode. D Shed logic never attempts to attain an actual mode of Auto or Cas if that mode is not permitted. Status Handling Output or readback fault detection is reflected in the status of PV [7], OUT [9], and BKCAL_OUT [25]. A limited SP [8] condition is reflected in the BKCAL_OUT [25] status.
Instruction Manual Blocks November 2014 D103434X012 input connector. In RemoteCascade (RCas) mode, the SP [8] comes from a host computer that writes to RCAS_IN [28]. The range and units of the SP [8] are defined by the PV_SCALE [11] attribute. In Manual (Man) mode the SP [8] automatically tracks the PV [7] value when you select the SP‐PV Track in Man I/O option in IO_OPTS [14]. You can disable this option in OOS mode only.
Instruction Manual Blocks November 2014 D103434X012 FSTATE_TIME [23]: The length of time, in seconds, that the AO block will wait to set Fault State. When Fault State is set, the OUT [9] value goes to either the FSTATE_VAL [24] value or holds its last position, depending on I/O_OPTS [14]. When the block has a target mode of CAS, a fault condition will be detected if the CAS_IN [17] has a BAD status or an Initiate Fault State substatus is received from the upstream block.
Instruction Manual Blocks November 2014 D103434X012 Application Information The configuration of an AO function block and its associated output channels depends on the specific application. A typical configuration for the Analog Output involves the following attributes: PV_SCALE Set the range and engineering units to values that correspond to the operation range. For the digital level controller, PV_SCALE [11] is typically set between 0 and 100%.
Instruction Manual Blocks November 2014 D103434X012 Analog Output (AO) Function Block D Read/Write Capability: RO ‐ Read Only, RW ‐ Read Write D Mode: The block mode(s) required to write to the parameter D Double indentations and shaded Index Numbers indicate sub‐parameters Table B‐27.
Instruction Manual Blocks November 2014 D103434X012 Table B‐27. Analog Output Function Block Parameter Definitions (Continued) Label PARAMETER_NAME Simulate SIMULATE Index Number RO / RW Block Mode Range Initial Value Description Data Type: DS‐82 Allows the analog input to be manually supplied when simulate is enabled. When simulation is disabled, the simulate value and status track actual value & status. 10 SIMULATE_STATUS 10.1 RW ALL 0 SIMULATE_VALUE 10.
Instruction Manual Blocks November 2014 D103434X012 Table B‐27. Analog Output Function Block Parameter Definitions (Continued) Label PARAMETER_NAME Index Number RO / RW Block Mode Range Initial Value Description Setpoint Rate Down SP_RATE_DN 18 ALL Positive, 0 disables rate limiting PV units +INF Data Type: Float Ramp rate for downward set point changes. When the ramp rate is set to zero, the set point is used immediately.
Instruction Manual Blocks November 2014 D103434X012 Table B‐27. Analog Output Function Block Parameter Definitions (Continued) Label PARAMETER_NAME Update Event UPDATE_EVT Index Number RO / RW Block Mode Range Initial Value 29 UNACKNOWLEDGED 29.1 RW NA 0:Undefined 1:Acknowledged 2:Unacknowledged 0: Undefined UPDATE_STATUS 29.2 RO NA 0:Undefined 1:Update reported 2:Update not reported 0: Undefined TIME_STAMP 29.3 RO NA 0 STATIC_REVISION 29.4 RO NA 0 RELATIVE_INDEX 29.
Instruction Manual Blocks November 2014 D103434X012 View Lists View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer. Table B‐28.
Instruction Manual Blocks November 2014 D103434X012 Field Communicator Menu Structure ANALOG OUTPUT FUNCTION BLOCK Quick Config Alert Key Process Value Scale: EU at 100% Process Value Scale: EU at 0% Process Value Scale: Units Index Process Value Scale: Decimal Simulate: Simulate Status Simulate: Simulate Value Simulate: Transducer Status Simulate: Transducer Value Simulate: Simulate En/Disable Setpoint: Status Setpoint: Value Setpoint High Limit Setpoint Low Limit Common Config Alert Key I/O Options Blo
Instruction Manual Blocks November 2014 D103434X012 Input Selector (ISEL) Function Block The Input Selector (ISEL) function block (figure B‐13) can be used to select the first good, maximum, minimum, average, or hot backup from as many as eight input values and place it at the output. The block supports signal status propagation. There is no process alarm detection in the Input Selector function block. Figure B‐14 illustrates the internal components of the ISEL function block.
Instruction Manual Blocks November 2014 D103434X012 Figure B‐14. Input Selector Function Block Schematic IN_1 IN_2 IN_3 AUTO Selection Algorithm IN_4 OUT MAN DISABLE_1 SELECTED DISABLE_2 DISABLE_4 OP_SELECT SEL_TYPE MIN_GOOD fieldbus−fbus_229a DISABLE_3 SELECT_TYPE NOTE: THIS FIGURE DOES NOT INCLUDE THE ADDITIONAL 4 INPUTS IN THE EXTENDED PARAMETERS.
Blocks Instruction Manual November 2014 D103434X012 Limit Propagation Refer to figure B‐15. When SELECT_TYPE [19] is Average, Not Limited is propagated unless all inputs have the same limit status. If all inputs have the same limit status, the limit status of the inputs is propagated.
Instruction Manual Blocks November 2014 D103434X012 Figure B‐15.
Instruction Manual Blocks November 2014 D103434X012 Figure B‐16.
Instruction Manual D103434X012 Blocks November 2014 Input Selection The ISEL function block reads the values and statuses of as many as eight inputs (IN_1 [11], IN_2 [12], IN_3 [13], IN_4 [14], IN_5 [25], IN_6 [26], IN_7 [27], IN_8 [28]). To use any of the six selection algorithms to select the output, OP_SELECT [22] must be 0.
Instruction Manual Blocks November 2014 D103434X012 For a SELECT_TYPE [19] of Average, SELECTED [21] indicates the number of inputs used in the average calculation. When the block mode is Manual, SELECTED [21] is set to 0. Alarm Detection A block alarm will be generated whenever the BLOCK_ERR [6] has an error bit set. The types of block error for the PID block are defined above. Process alarm detection is based on OUT [7] value.
Instruction Manual Blocks November 2014 D103434X012 Block Errors Table B‐33 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the ISEL block and are provided only for your reference. Table B‐33. BLOCK_ERR Conditions Condition Number Condition Name and Description 0 Other (NA) 1 Block Configuration Error ‐ If OP_SELECT is not being used, and SELECT_TYPE = 0. This implies OP_SELECT status is good and actual mode is AUTO.
Instruction Manual Blocks November 2014 D103434X012 Table B‐34. Input Selector Function Block Parameter Definitions (Continued) Label PARAMETER_NAME Block Mode MODE_BLK Index Number RO / RW Block Mode 5.1 ACTUAL PERMITTED NORMAL RW ALL 5.2 RO ALL 5.3 RW ALL 5.4 RW ALL Block Error BLOCK_ERR 6 Output OUT 7 Output Range OUT_RANGE 8 Grant Deny GRANT_DENY 9 RO NA MAN OOS ALL GRANT 9.1 ALL DENY 9.
Instruction Manual Blocks November 2014 D103434X012 Table B‐34. Input Selector Function Block Parameter Definitions (Continued) Label PARAMETER_NAME Index Number RO / RW Block Mode Range BAD NC constant Status Disable Analog Input 2 DISABLE_2 16 ALL Value 0=Use 1=Disable 17 ALL Value 0=Use 1=Disable 18 ALL 0 Data Type: Unsigned8 The minimum number of inputs which are “good” is less than the value of MIN_GOOD then set the OUT status to “bad”.
Instruction Manual Blocks November 2014 D103434X012 Table B‐34. Input Selector Function Block Parameter Definitions (Continued) Label PARAMETER_NAME Block Alarm BLOCK_ALM UNACKNOWLEDGED Index Number RO / RW Block Mode RW NA 0=Undefined 1=Acknowledged 2=Unacknowledged 0 0=Undefined 1=Clear reported 2=Clear not reported 3=Active reported 4=Active not reported 0 Range Initial Value Description 24 24.1 ALARM_STATE 24.2 RO NA TIME_STAMP 24.3 RO NA 0 SUBCODE 24.
Instruction Manual Blocks November 2014 D103434X012 Table B‐34. Input Selector Function Block Parameter Definitions (Continued) Label PARAMETER_NAME Alarm Summary ALARM_SUM Index Number RO / RW Block Mode Range Initial Value Description 34 CURRENT 34.1 RO NA UNACKNOWLEDGED 34.2 RO NA UNREPORTED 34.3 RO NA DISABLED 34.4 RW ALL Data Type: DS‐74 Current alert status, unacknowledged states, unreported states, and disabled states of the alarms associated with the function block.
Instruction Manual Blocks November 2014 D103434X012 Table B‐34. Input Selector Function Block Parameter Definitions (Continued) Label PARAMETER_NAME Low Alarm LO_ALM UNACKNOWLEDGED Index Number RO / RW Block Mode RW NA 0=Undefined 1=Acknowledged 2=Unacknowledged 0=Undefined 1=Clear reported 2=Clear not reported 3=Active reported 4=Active not reported Range Initial Value 47 47.1 0 ALARM_STATE 47.2 RO NA TIME_STAMP 47.3 RO NA 0 SUBCODE 47.4 RO NA 0 VALUE 47.
Instruction Manual Blocks November 2014 D103434X012 View Lists View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer. Table B‐35. ISEL Function Block, View 1 Index Number 1 Parameter ST_REV Table B‐37.
Instruction Manual Blocks November 2014 D103434X012 Field Communicator Menu Structure INPUT SELECTOR FUNCTION BLOCK Quick Config Alert Key Min Good Output Range: EU at 100% Output Range: EU at 0% Output Range: Units Index Output Range: Decimal Select Type Common Config Min Good Block Mode: Target Block Mode: Actual Block Mode: Permitted Block Mode: Normal Output Range: EU at 100% Output Range: EU at 0% Output Range: Units Index Output Range: Decimal Select Type Advanced Config Alert Key Static Revision S
Instruction Manual Blocks November 2014 D103434X012 Arithmetic (ARTH) Function Block The Arithmetic function block (figure B‐17) provides the ability to configure a range extension function for a primary input and applies the nine (9) different arithmetic types as compensation to or augmentation of the range extended input. All operations are selected by parameter and input connection. Figure B‐17.
Blocks Instruction Manual November 2014 D103434X012 Block Execution The Arithmetic function block provides range extension and compensation through nine (9) arithmetic types. There are two inputs (IN and IN_LO) used in calculating PV. PV is then combined with up to three inputs (IN_1, IN_2, and IN_3) through the user selected compensation function (ARITH_TYPE) to calculate the value of func. A gain is applied to func and then a bias is added to get the value PRE_OUT. In AUTO, PRE_OUT is used for OUT.
Instruction Manual D103434X012 Blocks November 2014 Figure B‐18. Arithmetic Function Block Schematic Different fluids over the same temperature range have different effects on level due to their thermal expansion coefficients. Vessel geometry also plays a major role. As the height of the vessel increases, the effect of thermal expansion becomes more apparent. Figure B‐19 shows the relative temperature effects on a level signal. Figure B‐19.
Blocks Instruction Manual November 2014 D103434X012 Compensation - Linear. This allows a ratio to be set up that increases the level indication at block output for an increase in the tank temperature relative to ambient temperature. This application can be applied to very large storage tanks whose contents are subject to thermal expansion and contraction during seasonal changes in temperature. Figure B‐20.
Instruction Manual D103434X012 Blocks November 2014 Compensation inputs which are not configured are not used in the calculation. PV is always used. If there is a divide by zero and the numerator is positive, func will be limited to COMP_HI; if the numerator is negative, func will be limited to COMP_LO. Block Errors Table B‐40 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are inactive for the ARTH block and are given here only for your reference.
Instruction Manual Blocks November 2014 D103434X012 Table B‐40. BLOCK_ERR Conditions Condition Number Condition Name and Description 0 Other - the output has a quality of uncertain. 1 Block Configuration Error ‐ the selected channel carries a measurement that is incompatible with the engineering units selected in XD_SCALE, the L_TYPE parameter is not configured, or CHANNEL = zero.
Instruction Manual Blocks November 2014 D103434X012 Table B‐42. Arithmetic Function Block Parameter Definitions Label PARAMETER_NAME Index Number RO / RW Block Mode Range Initial Value Description Data Type: Unsigned16 The revision level of the static data associated with the function block. The revision value will be incremented each time a static parameter value in the block is changed.
Instruction Manual Blocks November 2014 D103434X012 Table B‐42. Arithmetic Function Block Parameter Definitions (Continued) Label PARAMETER_NAME Index Number RO / RW Block Mode Range Initial Value Description Input Lo IN_LO 15 The value used for input whenever IN is below range. Input 1 IN_1 16 The first analog input value and status. Input 2 IN_2 17 The second analog input value and status. Input 3 IN_3 18 The third analog input value and status.
Instruction Manual Blocks November 2014 D103434X012 View Lists View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer. Table B‐43. ARTH Function Block, View 1 Index Number 1 Parameter Table B‐46.
Instruction Manual Blocks November 2014 D103434X012 Resource Block The resource block contains hardware specific characteristics associated with the device; it has no input or output parameters. Resource Block Parameters D Read/Write Capability: RO ‐ Read Only, RW ‐ Read Write D Mode: The block mode(s) required to write to the parameter D Double indentation and shaded Index Number indicates sub‐parameter Table B‐47.
Instruction Manual Blocks November 2014 D103434X012 Table B‐47. Resource Block Parameter Definitions (Continued) Label PARAMETER_NAME Index Number RO / RW Mode Range Initial Value Description Manufacturer Id MANUFAC_ID 10 RO 0x5100 Data Type: Unsigned32 Manufacturer identification number, used by an interface device or host to locate the DD file for the resource. All manufacturer identification numbers are maintained by the Fieldbus Foundation.
Instruction Manual Blocks November 2014 D103434X012 Table B‐47.
Instruction Manual Blocks November 2014 D103434X012 Table B‐47.
Instruction Manual Blocks November 2014 D103434X012 Table B‐47. Resource Block Parameter Definitions (Continued) Label PARAMETER_NAME Block Alarm BLOCK_ALM UNACKNOWLEDGED Index Number RO / RW Mode RW ALL 0: Undefined 1: Acknowledged 2: Unacknowledged 0: Undefined 0: Undefined 1: Clear (Reported) 2: Clear (Not Reported) 3: Active (Reported) 4: Active (Not Reported) 0: Undefined Range Initial Value 36 36.1 ALARM_STATE 36.2 RO NA TIME_STAMP 36.3 RO NA 0 SUBCODE 36.
Instruction Manual Blocks November 2014 D103434X012 Table B‐47. Resource Block Parameter Definitions (Continued) Label PARAMETER_NAME Index Number RO / RW Miscellaneous Options MISC_OPTIONS 45 RO Bit 0: Software download Firmware Revision FIRMWARE_REVISION 46 Mode Range Initial Value ‐ Description Data Type: Bit String Data Type: Uint8 Describes software revision information. This is the revision of the firmware that is currently in use. FIRMWARE_REV_MAJOR 46.
Instruction Manual Blocks November 2014 D103434X012 View Lists View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer. Table B‐48. Resource Block, View 1 Index Number 1 Parameter ST_REV 5.1 MODE_BLK.TARGET_MODE 5.
Instruction Manual Blocks November 2014 D103434X012 Transducer Block (Primary) Transducer blocks connect function blocks to local input/output functions. They read sensor hardware and write to effector (actuator) hardware. Transducer Block (Primary) Parameters D Read/Write Capability: RO ‐ Read Only, RW ‐ Read Write D Mode: The block mode(s) required to write to the parameter D Double indentation and shaded Index Number indicates sub‐parameter Table B‐54.
Instruction Manual Blocks November 2014 D103434X012 Table B‐54. Primary Transducer Block Parameter Definitions (Continued) Label PARAMETER_NAME Block Alarm BLOCK_ALM UNACKNOWLEDGED ALARM_STATE TIME_STAMP Index Number RO / RW Mode Range Initial Value Description 8 8.1 8.2 8.
Instruction Manual Blocks November 2014 D103434X012 Table B‐54. Primary Transducer Block Parameter Definitions (Continued) Label PARAMETER_NAME Index Number RO / RW Mode ENG_UNITS 17.3 RO OOS DECIMAL 17.4 RO OOS 18 RO NA Sensor Serial Number SENSOR_SN Range 1010: Meter 1012: cm 1013: mm 1018: ft. 1019: in.
Instruction Manual Blocks November 2014 D103434X012 Table B‐54. Primary Transducer Block Parameter Definitions (Continued) Label PARAMETER_NAME Index Number RO / RW Mode Range End Connection Style END_CONNECTION_STYLE 24.2 RW OOS 1: BW3 2: F1 3: F2 4: F3 5: F4 6: S1 7: S2 8: S3 9: S4 255: Unknown Torque Tube Wall TT_WALL 24.3 RW OOS 1: Thin 2: Standard 3: Heavy 255: Unknown Pressure Rating PRESSURE_RATING 24.4 RW OOS End Connection Type END_CONNECTION_TYPE 24.
Instruction Manual Blocks November 2014 D103434X012 Table B‐54. Primary Transducer Block Parameter Definitions (Continued) Label PARAMETER_NAME Index Number Digital Level Controller Units DLC_UNITS 25 Unit System UNIT_SYSTEM 25.1 RO / RW Mode Range Initial Value Description Data Type: DS‐269 Global units for primary transducer block RW AUTO 1: English 2: Metric 3: Mixed 2 Data Type: Enum (1) Unit System 1012: cm Data Type: Enum (2) Unit of length for displacer and driver rod.
Instruction Manual Blocks November 2014 D103434X012 Table B‐54.
Instruction Manual Blocks November 2014 D103434X012 Table B‐54. Primary Transducer Block Parameter Definitions (Continued) Label PARAMETER_NAME COMP_GAIN_2 COMP_TEMP_3 COMP_GAIN_3 COMP_TEMP_4 COMP_GAIN_4 COMP_TEMP_5 COMP_GAIN_5 COMP_TEMP_6 COMP_GAIN_6 COMP_TEMP_7 COMP_GAIN_7 COMP_TEMP_8 COMP_GAIN_8 COMP_TEMP_9 COMP_GAIN_9 COMP_TEMP_10 COMP_GAIN_10 Torque Tube Compensation TORQUE_TUBE_COMP STATUS Index Number RO / RW Mode 33.4 *RW OOS > = 0, < 2 1 33.
Instruction Manual Blocks November 2014 D103434X012 Table B‐54.
Instruction Manual Blocks November 2014 D103434X012 Table B‐54.
Instruction Manual Blocks November 2014 D103434X012 Table B‐54. Primary Transducer Block Parameter Definitions (Continued) Label PARAMETER_NAME DI_1_TRIP_PT DI_1_DEADBAND DI_1_ACTION DI_1_READBACK STATUS VALUE DI_2_TRIP_PT DI_2_DEADBAND DI_2_ACTION DI_2_READBACK STATUS VALUE SENSOR_MAJOR_REV SENSOR_MINOR_REV INSTRUMENT_SN Index Number RO / RW Mode 44 RW OOS NA 100% Data Type: Float Point where DI_1 will trip based on PRIMARY_VALUE_RANGE 45 RW OOS < 99.
Instruction Manual Blocks November 2014 D103434X012 Table B‐54. Primary Transducer Block Parameter Definitions (Continued) Label PARAMETER_NAME Index Number Failed Active FAILED_ACTIVE 61 Failed Alarm FAILED_ALM 62 UNACKNOWLEDGED 62.
Instruction Manual Blocks November 2014 D103434X012 Table B‐54. Primary Transducer Block Parameter Definitions (Continued) Label PARAMETER_NAME Index Number RO / RW Mode Range Initial Value TIME_STAMP 67.3 RO NA NA SUBCODE 67.4 RO NA NA VALUE 67.5 RO NA NA 68 RW AUTO 0 to 15 2 Data Type: Uint8 Advise alert priority AUTO 1: 2: 3: 4: 5: 6: 7: 8: 2: 3: 6: 7: 8: Data Type: BIT_ENUM (4) Advise alert enable. Enable allows detection of alert. All alerts can be disabled.
Instruction Manual Blocks November 2014 D103434X012 Table B‐54. Primary Transducer Block Parameter Definitions (Continued) Label PARAMETER_NAME PRESSURE_SELECT COMP_PRESSURE STATUS VALUE GAS_MOL_WGT DEVICE_HISTORY MAX_RECORDED_TEMP MIN_RECORDED_TEMP TIME_OVER_UTL TIME_UNDER_LTL TEMP_INTEGRAL RUN_TIME TIME_SINCE_RESET CHAR_ARRAY INT_ARRAY LONG_ARRAY FLOAT_ARRAY STRING_RESERVED RESERVED Index Number RO / RW Mode 76 RW OOS 77 RW 77.1 RO 77.
Instruction Manual Blocks November 2014 D103434X012 View Lists View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer. Table B‐55. Primary Transducer Block, View 1 Index Number 1 Parameter ST_REV Table B‐57.
Instruction Manual Blocks November 2014 D103434X012 Note Because individual views are limited in size, View List 4 has four parts. Table B‐58. Primary Transducer Block, View 4.1 Index Number Parameter 1 ST_REV 3 STRATEGY 4 ALERT_KEY 10 TRANSDUCER_TYPE 18 SENSOR_SN 19 SENSOR_CAL_METHOD 20 SENSOR_CAL_LOC 21 SENSOR_CAL_DATE 22 SENSOR_CAL_WHO Table B‐59. Primary Transducer Block, View 4.2 Index Number 1 Parameter ST_REV 15.1 PRIMARY_VALUE_RANGE.EU_100 15.2 PRIMARY_VALUE_RANGE.
Instruction Manual Blocks November 2014 D103434X012 Transducer Block (LCD) The LCD transducer block is used to configure DLC3020f display properties. It has no affect on the reported PV. LCD Transducer Block Parameters D Read/Write Capability: RO ‐ Read Only, RW ‐ Read Write D Mode: The block mode(s) required to write to the parameter D Double indentation and shaded Index Number indicates sub‐parameter Table B‐62.
Instruction Manual Blocks November 2014 D103434X012 Table B‐62. LCD Transducer Block Parameter Definitions (Continued) Label PARAMETER_NAME Index Number RO / RW Range Default Value 12 DISPLAY_PV VALUE STATUS Data Type: DS‐65 12.1 *RO NA NA 12.2 RO NA NA Data Type: Float PV in units selected above including display offset if it applies.
Instruction Manual Blocks November 2014 D103434X012 Field Communicator Menu Tree (Resource and Transducer Blocks) Bold Italic text = Method Check Status Home Overview Configure Service Tools Advanced Overview Overview Check Status Primary Purpose Variables Shortcuts Device Status: Good Failed Maintenance or Advisory Mode Status: In Service or Not in Service Shortcuts Device Information Calibration/Setup Logs Device Overview Device Information Device Overview Version Information Manufacturing Inform
Instruction Manual Blocks November 2014 D103434X012 Bold Italic text = Method Manual Setup (continued) Process Fluid Fluid Name Density in Use Process Fluid (Level only) Manual Setup > Process Fluid (Level only) Mode Device Process Fluid (Level only) Process Fluids (Interface only) Instrument Display Snap Acting Control Options Process Fluid Change Process Fluid Temperature Compensation Density Table Temperature Compensation Density Table Temperature 1 Density 1 Temperature 2 Density 2 .... .... ...
Instruction Manual Blocks November 2014 D103434X012 Bold Italic text = Method Manual Setup (continued) Manual Setup > Snap Acting Control Mode Device Process Fluid (Level) Process Fluids (Interface) Instrument Display Snap Acting Control Options Snap Acting Control Primary Value Primary Value Percent Snap Acting Control Snap Units DI1 Trip Point Settings DI2 Trip Point Settings DI1 Trip Point Settings DI1 Action DI1 Trip Point DI1 Deadband DI1 Readback DI2 Trip Point Settings DI2 Action DI2 Trip Point
Instruction Manual Blocks November 2014 D103434X012 Bold Italic text = Method Home Overview Configure Service Tools Advanced Alert Setup Configure Instrument Setup Manual Setup Alert Setup Calibrate PlantWeb Alert Enable Alert Setup Failed Enable Maintenance Enable Advisory Enable Rapid Rate Limit (length/sec) Clear Rate Limit Alert PlantWeb Alert Enable PlantWeb Alert Reporting PlantWeb Alert Reporting Failed Suppress Maintenance Suppress Advisory Suppress Calibrate Home Overview Configure Servic
Blocks November 2014 178 Instruction Manual D103434X012
Instruction Manual FOUNDATION fieldbus Communication D103434X012 November 2014 Appendix C FOUNDATION fieldbus CommunicationC‐ FOUNDATION Fieldbus Communication DLC3020f digital level controllers use the FOUNDATION fieldbus to communicate with other fieldbus instruments and the control system. Fieldbus is an all digital, serial, two‐way communication system which interconnects “field” equipment such as transmitters, digital level controllers, and process controllers.
Instruction Manual FOUNDATION fieldbus Communication November 2014 D103434X012 input and output parameters. However, they may be accessed and modified remotely, as specified by the function block. Figure C‐1 illustrates the internal structure of a function block. When execution begins, input parameter values from other blocks are snapped‐in by the block. The input snap process ensures that these values do not change during the block execution.
Instruction Manual FOUNDATION fieldbus Communication November 2014 D103434X012 data from sensors and ensure proper writes to the actuator without burdening the function blocks that use the data. The transducer block also isolates the function block from the specific characteristics of the physical I/O. Block Modes All blocks have modes. The mode determines the source of the set point, the destination of the output, how the block executes, and the relationship between setpoint and output.
Instruction Manual FOUNDATION fieldbus Communication November 2014 D103434X012 Figure C‐2. Block Hierarchy Example RESOURCE BLOCK PID BLOCK ANALOG OUTPUT (AO) BLOCK TRANSDUCER BLOCK NOTES: 1. CHANGING THE RESOURCE BLOCK TO OUT OF SERVICE CHANGES ALL FUNCTION BLOCKS TO OUT OF SERVICE, BUT DOES NOT AFFECT THE TRANSDUCER BLOCK. 2. CHANGING A DOWNSTREAM BLOCK TO OUT OF SERVICE AFFECTS THE UP STREAM BLOCK.
Instruction Manual FOUNDATION fieldbus Communication November 2014 D103434X012 Remote Cascade (RCas)—The block performs the specified calculations based on a set point from a host computer or others via the remote cascade input and outputs the result. If the block has any outputs, these continue to update. Examples of Modes for Various Operational Statuses Table C‐2 shows examples of block mode combinations in a digital level controller (however it does not show all combinations).
Instruction Manual FOUNDATION fieldbus Communication November 2014 D103434X012 Table C‐3.
Instruction Manual FOUNDATION fieldbus Communication November 2014 D103434X012 Limit Propagation The following describes limit propagation: AO Block D If the valve position is below the low cutoff value, the AO block READBACK status limit is LOW_LIMITED. D If the valve position is above the high cutoff value, the AO block READBACK status limit is HIGH_LIMITED. D If the transducer block actual mode is Auto and the above conditions are not true, the AO block READBACK status limit is NOT_LIMITED.
FOUNDATION fieldbus Communication November 2014 Instruction Manual D103434X012 D recognizes and adds new devices to the link. D removes non‐responsive devices from the link. D distributes Data Link (DL) and Link Scheduling (LS) time on the link. Data Link Time is a network‐wide time periodically distributed by the LAS to synchronize all device clocks on the bus. Link Scheduling time is a link‐specific time represented as an offset from Data Link Time.
Instruction Manual FOUNDATION fieldbus Communication November 2014 D103434X012 Figure C‐4. Scheduled Data Transfer Host System LAS Schedule X Y Z DT(A ) A B C A D A P S P S P S CD (X, A) LAS=Link Active Scheduler P=Publisher S=Subscriber CD=Compel Data DT=Data Transfer Packet Device X Device Y Device Z B2713‐1 Unscheduled Transfers Figure C‐5 diagrams an unscheduled transfer.
Instruction Manual FOUNDATION fieldbus Communication November 2014 D103434X012 D Report Distribution: This type of communication is used to broadcast and multicast event and trend reports. D Client/Server: This type of communication is used for request/ response exchanges between pairs of devices, such as a set point change. Like Report Distribution reporting, the transfers are queued, unscheduled, and prioritized.
Instruction Manual Glossary November 2014 D103434X012 Glossary Alarm Deadband The amount by which the process variable must return within normal limits for the alarm to clear. Alarm Limit An adjustable value that, when exceeded, activates an alert. Algorithm A set of logical steps to solve a problem or accomplish a task. A computer program contains one or more algorithms. Control Loop An arrangement of physical and electronic components for process control.
Instruction Manual Glossary November 2014 Gain The ratio of output change to input change. Hardware Revision Revision number of the Fisher instrument hardware. The physical components of the instrument are defined as the hardware. D103434X012 Non‐Volatile Memory (NVM) A type of semiconductor memory that retains its contents even though power is disconnected. NVM contents can be changed during configuration unlike ROM which can be changed only at time of instrument manufacture.
Instruction Manual Glossary November 2014 D103434X012 Reranging Configuration function that changes the digital level controller 4 to 20 mA settings. RTD The abbreviation for resistance temperature detector. Temperature is measured by the RTD by correlating the resistance of the RTD element with temperature. Send Data A Field Communicator command that transfers configuration data from the Field Communicator's working register to the digital level controller memory.
Glossary November 2014 192 Instruction Manual D103434X012
Instruction Manual Index November 2014 D103434X012 Index A Addressing, 185 Alarm Detection AI Block, 73 DI Block, 106 ISEL Block, 132 PID Block, 90 Ambient Temperature, Operative, 249 Sensors, 8 AMS Suite: Intelligent Device Manager, 3 Analog Input (AI) Block Advanced Features, 77 Alarm Priorities, 74 Block Errors, 77, 145 Block Modes, 73 Channel Selections, 75, 118 Field Communicator Menu Structure, 84 Filtering, 75 Parameters, 79 Signal Conversion, 76 Direct, 76 Indirect, 76 Indirect Square Root, 76 Si
Instruction Manual Index November 2014 Report Distribution, 188 Unscheduled Transfers, 187 D103434X012 F Device Description (DD), Description, 183 Feedforward, Calculation, 89 Device Overview, 22 Field Communicator Menu Structure Analog Input Function Block, 84 Analog Output Function Block, 125 Discrete Input Function Block, 112 Input Selector Function Block, 140 PID Function Block, 102 Diagnostics, 7 Direct Action, 90 Arithemetic (ARTH) Block, View lists, 149 Discrete Input (DI) Block, 104 Action
Instruction Manual Index November 2014 D103434X012 BLOCK_ERR Conditions, 133 Direct Selection of Inputs, 131 Disabling Inputs, 131 Field Communicator Menu Structure, 140 Identification of Selected Inputs, 131 Input Selection, 131 Modes, 126 Parameter List, 133 Status Handling Limit Propagation, 128 Quality Use and Propagation, 127 Substatus Propagation, 128 STATUS_OPTS Supported, 128 View lists, 139 Input Signal, 249 Series, 8 Installation DLC3020f on 249 Sensor, 15 Heat Insulator, 16 Of 249 Sensor, 13 I
Instruction Manual Index November 2014 Shed Options, 87 Status Handling, 88 Tracking, 89 View lists, 100 D103434X012 Subscriber (S), 186 Supply Requirements, DLC3020f, 6 System Management, 186 PlantWeb Alerts, 39 Pressure Boundary Materials, allowable process temperatures, 8 Principle of Operation, DLC3020f, 71 Publisher (P), 186 R Related Documents, 5 Repeatability, 6 Resource Block Definition, 180 Field Communicator Menu Tree, 174 View lists, 156 Reverse Action, 90 reverse polarity protection, 71 S
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Fisher, FIELDVUE, and DeltaV are marks owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co.