Quick Start Guide

Quick Start Guide
D103214X012
DLC3010 Digital Level Controller
September 2014
33
Figure 15. FM Loop Schematic
28B5745‐C
1. THE INSTALLATION MUST BE IN ACCORDANCE WITH
 THE NATIONAL ELECTRIC CODE (NEC), NFPA 70, ARTICLE
 504 AND ANSI/ISA RP12.6.
2. CLASS 1, DIV 2 APPLICATIONS MUST BE INSTALLED AS SPECIFIED
 IN NEC ARTICLE 501-4(B). EQUIPMENT AND FIELD WIRING IS
 NON-INCENDIVE WHEN CONNECTED TO APPROVED BARRIERS WITH
 ENTITY PARAMETERS.
3. LOOPS MUST BE CONNECTED ACCORDING TO THE BARRIER
 MANUFACTURERS INSTRUCTIONS.
4. MAXIMUM SAFE AREA VOLTAGE SHOULD NOT EXCEED 250 Vrms.
5. RESISTANCE BETWEEN BARRIER GROUND AND EARTH GROUND
 MUST BE LESS THAN ONE OHM.
6. NORMAL OPERATING CONDITIONS 30 VDC 20 mADC.
7. IF HAND-HELD COMMUNICATOR OR MULTIPLEXER IS USED,
 IT MUST BE FM APPROVED AND INSTALLED PER THE
 MANUFACTURE'S CONTROL DRAWING.
8. FOR ENTITY INSTALLATION (I.S. AND N.I.);
Vmax > Voc, or Vt Ci + Ccable < Ca
Imax > Isc, or It Li + Lcable < La
Pi > Po, or Pt
9. THE APPARATUS ENCLOSURE CONTAINS ALUMINUM AND IS
 CONSIDERED TO CONSTITUTE A POTENTIAL RISK OF IGNITION
 BY IMPACT OR FRICTION. AVOID IMPACT AND FRICTION DURING
 INSTALLATION AND USE TO PREVENT RISK OF IGNITION.
HAZARDOUS LOCATION
I.S. CLASS I,II,III DIV 1, GROUPS A,B,C,D,E,F,G
N.I. CLASS I, DIV 2, GROUPS A,B,C,D
NON-HAZARDOUS LOCATION
FM APPROVED BARRIER
SEE NOTE 7
FISHER TYPE DLC3010
Vmax = 30 VDC
Imax = 226 mA
Ci - 5.5 nF
Li = 0.4 mH
Pi = 1.4 W