Quick Start Guide

Quick Start Guide
D103214X012
DLC3010 Digital Level Controller
September 2014
11
Figure 5. Typical Mounting Positions for FIELDVUE DLC3010 Digital Level Controller on Fisher 249 Sensor
8
2
4
6
3
7
1
5
SENSOR
CAGED
CAGELESS
RIGHT‐OF‐DISPLACER
LEFT‐OF‐DISPLACER
1
1
1 NOT AVAILABLE FOR SIZE NPS 2 CL300 AND CL600 249C SENSOR.
19B2787 Rev. D
19B6600 Rev. C
B1407‐2
8
2
4
6
1
3
7
5
Figure 6. Close‐up of Set‐Screw
SET‐SCREW
4. Position the digital level controller so the access hole is on the bottom of the instrument.
5. Carefully slide the mounting studs into the sensor mounting holes until the digital level controller is snug against
the sensor.
6. Reinstall the hex nuts on the mounting studs and tighten the hex nuts to 10 NSm (88.5 lbfSin).