Figure 9. Displacer and Displacer Rod Connections
LOCKING NUTS
DISPLACER SPUD
DISPLACER
STEM
EXTENSION
DISPLACER
STEM END
PIECE
DISPLACER ROD
COTTER SPRING
Figure 10. Positioning Fisher 249W Wafer Body on
the Connecting Flange
W8224
Note
In the next step, if mounting the wafer body on a displacer cage and a flange adaptor is required, install the flange adaptor instead
of the blind flange.
5. Refer to figure 11. Place a second seal on top of the wafer body. Place a blind flange on the wafer body so that the
holes in the blind flange align with the holes in the connecting flange.
6. Refer to figure 12. Secure the wafer body between the blind flange and connecting flange by inserting the
remaining studs and nuts. Tighten the nuts just enough to hold the wafer body in place.
7. Remove the nut from the stud that was used in step 2. Reinsert the stud so it passes through the holes in the blind
flange and connecting flange. Thread the nut back onto the stud.
8. Tighten all nuts in a crisscross fashion to the torque recommended in tables 2 or 3.
Figure 11. Blind Flange Installation
W8225
Figure 12. Fisher 249W Installation Complete
W8227