Data Sheet

DLC3010 Digital Level Controller
D102727X012
Product Bulletin
11.2:DLC3010
August 2014
15
Table 8. Hazardous Area Classifications for Canada—CSA
Certification Body Certification Obtained Entity Rating Temperature Code
CSA
Intrinsically Safe
Class I,II,III Division 1 GP A,B,C,D,E,F,G
per drawing 28B5744 T6
Vmax = 30 VDC
Imax = 226 mA
Ci = 5.5 nF
Li = 0.4 mH
T6 (Tamb ≤ 80°C)
Explosion-proof
Class I, Division 1 GP B,C,D T6
- - - T6 (Tamb ≤ 80_C)
Class I Division 2 GP A,B,C,D T6
Class II Division 1, 2 GP E,F,G T6
Class III
- - - T6 (Tamb ≤ 80°C)
Table 9. Hazardous Area Classifications for United States—FM
Certification Body Certification Obtained Entity Rating Temperature Code
FM
Intrinsically Safe
Class I,II,III Division 1 GP A,B,C,D,E,F,G
per drawing 28B5745 T5
Vmax = 30 VDC
Imax = 226 mA
Pi = 1.4 W
Ci = 5.5 nF
Li = 0.4 mH
T5 (Tamb ≤ 80°C)
Explosion-proof
Class I, Division 1 GP A,B,C,D
- - - T5 (Tamb ≤ 80_C)
Class I Division 2 GP A,B,C,D
Class II Division 1 GP E,F,G
Class II Division 2 GP F,G
- - - T5 (Tamb ≤ 80°C)
Table 10. Hazardous Area Classifications—ATEX
Certificate Certification Obtained Entity Rating Temperature Code
ATEX
Intrinsically Safe
II 1 G D
Gas
Ex ia IIC T5 Ga
Dust
Ex ia IIIC T83_C Da IP66
Ui = 30 VDC
Ii = 226 mA
Pi = 1.4 W
Ci = 5.5 nF
Li = 0.4 mH
T5 (Tamb ≤ 80_C)
Flameproof
II 2 G D
Gas
Ex d IIC T5 Gb
Dust
Ex tb IIIC T83_C Db IP66
- - - T5 (Tamb ≤ 80_C)
Type n
II 3 G D
Gas
Ex nA IIC T5 Gc
Dust
Ex t IIIC T83_C Dc IP66
- - - T5 (Tamb ≤ 80_C)