Table 5. Fault Register Fault Flags Summary Table
Diagnostic Flags Bit
Mask Value
Diagnostic Flags Binary Mask Value Description
0x8001 1000 0000 0000 0000 Fault in N.V. Memory system has restored default settings
0x4000 0100 0000 0000 0000 Motor assembly stall
0x2000 0010 0000 0000 0000 Speed measurement fault
0x1000 0001 0000 0000 0000 System or Watchdog fault
0x0800 0000 1000 0000 0000 Overspeed condition
0x0400 0000 0100 0000 0000 Calibration span not in legal range
0x0200 0000 0010 0000 0000 Fault in N.V. Memory system has recovered settings
0x0100 0000 0001 0000 0000 Communications Timeout
0x0080 0000 0000 1000 0000 Valve was shutdown while moving
0x0040 0000 0000 0100 0000 Valve span calibrated (informational)
0x0020 0000 0000 0010 0000 Valve position controller active (informational)
0x0010 0000 0000 0001 0000 Analog input below 3mA/0.75V (informational)
0x0008 0000 0000 0000 1000 Motor Overspeed coast condition
0x0004 0000 0000 0000 0100 Modbuscommandhasbeensent(startsacalibratedsystem)
0x0002 0000 0000 0000 0010 Analog input initialized (system has seen input >3mA/1V
0x0001 0000 0000 0000 0001 Start delay active (within 10 second calibration window)
A.2 Diagnostic Flags
The diagnostic register holds a 16 bit value that represents 16 individual flags, when set (value ‘1’), this indicates the
following conditions have occurred or are still present, the highest 7 bits are latching and will be present in t he register
even if the initial cause for the flag being set is removed. If these flags are set, a reset needs to be performed to clear
the fault.
A.2.1 Fault in NV Memory
This is a severe fault and is usually seen when the firmware is upgraded with a program that uses a different
EEPROM/Non-volatile memory map. If this is not the case then the probable c ause is a fault in the memory hardware.
A.2.2 M otor Assembly Stall
Thevalveplugwasunabletomovetothecommandedposition.Thedrivehasattemptedtomovethemotorby
applying a non-zero PWM signal, and the speed has not been detected as greater than 0 with a 400ms period. This
fault latches and needs to be reset.
A.2.3 Speed Measurement Fault
The controller detected pulses that correspond to the motor going much faster than the speed the speed
measurement system is designed for the integrity of the measurement cannot be relied upon. This fault latches and
needs to be reset.
A.2.4 System or Watchdog Fault
The software system has been reset and this flag is set at power up if the case of the reset was the onboard watchdog
either timing out OR being forced by program function call. This flag is used as an indication that this type of reset has
occurred.