Data Sheet
DandDAValves
D100039X012
Product Bulletin
51.2:D
March 2014
5
Installation
Valve orientation of the D and DA does n ot affect
operation, but to facilitate changing trim parts, the
valvestemshouldbeverticalwiththeactuatorabove
the valve. Proper flow direction is indicated by the
arrow on the valve.
Dimensions are shown in figures 2 and 3.
Ordering Information
When ordering, specify:
Application
1. Type of application
a. Throttling or on-off
b. Reducing or relief
2. Controlled fluid (include chemical analysis of fluid, if
possible)
3. Specific gravity of controlled fluid
4. Fluid temperature
5. Range of flowing inlet pressure
6. Pressure drops
a. Range of flowing pressure drops
b. Maximum at shutoff
7. Flow rates
a. Minimum controlled flow
b. Normal flow
c. Maximum flow
8. Maximum permissible noise level, if critical
9. Shutoff classification required
10. Linesizeandschedule
Valve
Refer to the specifications. Review the description for
each specification. Indicate the desired choice
whenever there is a selection (
J)tobemade.Always
indicate the valve body design being ordered as
identified in the available c onfiguration specification.
Actuator and Accessories
Refer to separate bulletins covering actuators and
accessories for ordering information.