Data Sheet

3610J and 3620J Positioners
D200064X012
Product Bulletin
62.1:3610
February 2015
11
Table 3. Hazardous Area Classifications for Fisher 3622 Electro-Pneumatic Converter
(1)
—CSA (Canada)
Certification Body Certification Obtained Entity Rating Temperature Code
CSA
Intrinsically Safe
Ex ia IIC T4/T5/T6 per drawing GE28591
Ex ia Intrinsically Safe
Class I, II Division 1 GP A,B,C,D,E,F,G T4/T5/T6
per drawing GE28591
Vmax = 30 VDC
Imax = 150 mA
Pi = 1.25 W
Ci = 0 nF
Li = 0 mH
T4 (Tamb ≤ 82°C)
T5 (Tamb
≤ 62°C)
T6 (Tamb
≤ 47°C)
Explosion-proof
Ex d IIC T5
Class I, Division 1, GP A,B,C,D T5
- - -
T5 (Tamb ≤ 82°C)
Type n
Ex nA IIC T6
- - -
T6 (Tamb ≤ 82°C)
Class I, Division 2, GP A,B,C,D T6
- - -
T6 (Tamb ≤ 82°C)
Class II, Division 1, GP E,F,G T5
T5 (Tamb ≤ 82°C)
Class II, Division 2, GP F,G T6
T6 (Tamb ≤ 82°C)
1. These hazardous area classification also apply to 3620J positioners.
Table 4. Hazardous Area Classifications for Fisher 3622 Electro-Pneumatic Converter
(1)
—FM (United States)
Certification Body Certification Obtained Entity Rating Temperature Code
FM
Intrinsically Safe
Class I Zone 0 AEx ia IIC T4/T5/T6 per drawing GE28590
Class I, II, III Division 1 GP A,B,C,D,E,F,G T4/T5/T6
per drawing GE28590
Vmax = 30 VDC
Imax = 150 mA
Pi = 1.25 W
Ci = 0 nF
Li = 0 mH
T4 (Tamb ≤ 82°C)
T5 (Tamb
≤ 62°C)
T6 (Tamb
≤ 47°C)
Explosion-proof
Class I Zone 1 AEx d IIC T5
Class I, Division I, GP A,B,C,D T5
- - -
T5 (Tamb ≤ 82°C)
Type n
Class I Zone 2 AEx nA IIC T5
- - -
T5 (Tamb ≤ 82°C)
Class I, Division 2, GP A,B,C,D T5
Class II, Division 1, GP E,F,G T5
Class II, Division 2, GP F,G T5
- - -
T5 (Tamb ≤ 82°C)
1. These hazardous area classification also apply to 3620J positioners.
Table 5. Hazardous Area Classifications for Fisher 3622 Electro-Pneumatic Converter
(1)
—ATEX
Certificate Certification Obtained Entity Rating Temperature Code
ATEX
II 1 G & D
Intrinsically Safe
Gas
Ex ia IIC T4/T5/T6 Ga
Ui = 30 VDC
Ii = 150 mA
Pi = 1.25 W
Ci = 0 nF
Li = 0 mH
T4 (Tamb ≤ 82°C)
T5 (Tamb
≤ 62°C)
T6 (Tamb
≤ 47°C)
Dust
Ex ia IIIC Da T120°C (Tamb
≤ 82°C)/ T100°C (Tamb ≤ 62°C) /
T85°C (Tamb
≤ 47°C)
- - -
II 2 G & D
Flameproof
Gas
Ex d IIC T5 Gb
- - -
T5 (Tamb ≤ 82°C)
Dust
Ex tb IIIC Db T82°C (Tamb
≤ 79°C)
- - -
II 3 G & D
Type n
Gas
Ex nA IIC T6 Gc
- - -
T6 (Tamb ≤ 82°C)
Dust
Ex tc IIIC Dc T85°C (Tamb
≤ 82°C)
- - -
1. These hazardous area classification also apply to 3620J positioners.