Brochures and Data Sheets

22
Data/Signal Line Protection
General Technical Specifications
Operating Voltage 5, 12, 24, 48, 65 VDC
Clamping Voltage 8, 15, 30, 60, 75 VDC
Operating Current 1.5 A
Peak Surge Current (10 x 1000 µs) 008 = 125 A, 015 = 72 A,
030 = 22 A, 060 = 18 A, POE*=15 A
Frequency Range 0—100 MHz
Insertion Loss < 0.1 dB at 50 MHz
SPD Technology Silicon Avalanche Diode (SAD)
Connection Type RJ-45 Jacks
Operating Temperature -40°C to +85°C
Dimensions (Inches) 1.0H x 2.5W x 4.25L
Weight 3 oz
Certifications UL 497B (*except LCDP-POE)
The user equipment plugs into the LCDP’s equipment (protected) side,
and the LCDP’s line (unprotected) side is connected to the incoming line.
All 8 conductors are protected. The green ground wire must be bonded
to the protected equipment power ground (third wire, green wire safety
ground). Do not add length to the ground wire, for it must be kept as
short as possible.
Ordering Information
LCDP-008 8 Volts
LCDP-015 15 Volts
LCDP-030 30 Volts
LCDP-060 60 Volts
LCDP-POE 75 Volts
Installation
Features
<1 nanosecond response time
Line-to-line protection
Low capacitance
RJ-45/4 pair protection (8 wire)
Silicon avalanche design
Line to ground protection
5 year warranty
Edco LCDP Series
Data Circuit Protection
The Edco LCDP Series is designed to conveniently protect 8 wire, low voltage data
circuits and employs two RJ-45 jacks for easy installation. The Edco LCDP utilizes
silicon avalanche (solid-state) suppression technology, and exhibits very low
capacitance to accommodate high data rates. This unit supports high-speed data
rates of over 100 Mbps.