Brochures and Data Sheets

Edco PHC Series
Two-Pair Signaling Circuit Protector (Modular)
The Edco PHC Series is designed to protect two pairs of wires specifically
for alarm and security systems where operating currents can be as high
as 5 Amps. Electrically, the Edco PHC Series is a rugged series hybrid
implementing a staged complement of MOVs, copper wound inductors and
Silicon Avalanche Diodes. This design reduces series resistance to 0.2 Ohms
per pair. These products are intended to mate with an Edco PCB1B
gold-plated female terminal connector.
The Edco PHC modules plug into a base assembly (Edco PCB1B). The base
assembly can be mounted to any flat surface and should be located as close
as practical to the protected equipment. Terminal 1 and/or terminal 10
should be connected to Building-Approved Ground with 12 or 10 gauge
solid wire.
General Technical Specifications
Ordering Information
Features
Three-stage protection
Differential protection
Common mode protection
Plug-in module
Automatic recovery
Fast response time
Continuous current up to 5 Amps
UL 497B listed
Requires Edco PCB1B base
PC642PTU (Pass Thru Unit)
available for troubleshooting
5 year warranty
Operating Voltage 12, 18, 24, 36, 52, 60, 120 VDC
Clamping Voltage 15, 20, 30, 43, 60, 70, 150 VDC
Operating Current 5 A
Peak Surge Current 10 kA (8 x 20 µs)
Frequency Range 0–10 MHz
Insertion Loss < 0.1 dB at 10 MHz
SPD Technology MOV, SAD, w/Series Inductor
Connection Type Terminal block
w/compression lugs
Terminals accept up to 10 AWG
Operating Temperature -40°C to +85°C
Dimensions (Inches) 3.7H x 1.75W x 2.375L
(PHC + PCB1B Base)
Weight 8 oz
Certifications UL 497B
24V Horn, Strobe, Bell: PHC-043 & PCB1B
70V Speaker Lines: PHC-SP70 & PCB1B
EDCO PCB1B BASE SOLD SEPARATELY
PCB1B:
Unprotected Pair 2
Unprotected Pair 1
Protected Pair 2
Protected Pair 1
Keying Pin
Even TerminalsOdd Terminals
Field Side
Electronics Side
9
7
5
3
1
10
8
6
4
2
1.0
{
}
}
{
2.125"
2.4"
Ground Terminal 1 or 10 to Buil ding A pproved Ground
Terminal Assignments
015
020
030
043
060
S P 7 0
130 R M S
15 Volts
20 Volts
30 Volts
43 Volts
60 Volts
*100 Volts
*150 Volts
*Not UL Listed
(For Horn, Bell, Strobes)
(For 120V Signal Lines)
VOLTAGE CLAMP
P H C
Applications Part Number
Dimensions
DO NOT daisy chain grounds. NOT intended for shield
termination. Install ground in accordance with all
applicable codes.
How to Specify the Appropriate Model
14
Data/Signal Line Protection