Technical data
Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW)
36
2.5.6 Liebert Local Monitoring Systems, Autochangeover and Leak Detection
Provide indicated quantities of the following:
• ______ Leak Detection System(s) Model __________________________________
• ______ Remote Monitor(s) Model ________________________________________
• ______ Auto Changeover Control(s) Model ________________________________
2.5.7 Liebert SiteScan Site Monitoring System
A Liebert SiteScan Site Monitoring System Model __________________ shall be provided for remote
monitoring of the Liebert DataMate unit and monitoring of other Liebert support equipment. The Lie-
bert SiteScan shall have the capability to monitor and change (at the user direction) the temperature
and humidity setpoints and sensitivities of each unit. The printer shall provide the user with chrono-
logical alarm information. It shall also be capable of being programmed to print out environmental
conditions or operating modes at each unit.
2.5.8 Drycooler
The Liebert drycooler shall be a low-profile, direct-drive propeller fan-type air-cooled unit. The dry-
cooler shall be constructed with an aluminum cabinet and a copper-tube aluminum fin coil, and one or
more direct drive fans. All electrical connections and controls shall be enclosed in an integral, NEMA
3R rated electrical panel section of the drycooler. The drycooler shall be quiet and corrosion resistant.
The drycooler shall be designed for _____°F (°C) ambient.
2.5.9 Glycol Pump Package
The system shall include a centrifugal pump mounted in a weatherproof and vented enclosure. The
pump shall be rated for ____ gpm (l/s) at ____ ft. (kPa) of head, and operate on _____ volt, ____ phase,
______ Hz.
3.0 EXECUTION
3.1 Installation of Air Conditioning Units
3.1.1 General
Install Air Conditioning units in accordance with manufacturer's installation instructions. Install
units plumb and level, firmly anchored in locations indicated, and maintain manufacturer's recom-
mended clearances.
3.1.2 Electrical Wiring
Install and connect electrical devices furnished by manufacturer but not specified to be factory
mounted. Furnish copy of manufacturer's electrical connection diagram submittal to electrical con-
tractor.
3.1.3 Piping Connections
Install and connect devices furnished by manufacturer but not specified to be factory mounted. Fur-
nish copy of manufacturer's piping connection diagram submittal to piping contractor.
3.1.4 Supply and Drain Water Piping
Connect water supply and drains to air conditioning unit. Provide pitch and trap as manufacturer's
instructions and local codes require.
3.2 Field Quality Control
Startup airconditioning units in accordance with manufacturer's start up instructions. Test controls
and demonstrate compliance with requirements.