Technical data
Chilled Water Systems
21
Figure 12 General arrangement—Chilled water systems
Table 14 Chilled water capacity correction factors based on 10°F (5.6°C) water rise
EWT
72°F (22.2°C) 50% 75°F (23.9°C) 45%RH
TCC SCC TCC SCC
42°F (5.6°C) 1.27 1.14 1.23 1.11
43°F (6.1°C) 1.17 1.09 1.15 1.07
44°F (6.7°C) 1.08 1.04 1.07 1.04
45°F (7.2°C) 1.00 1.00 1.00 1.00
46°F (7.8°C) 0.93 0.96 0.94 0.96
47°F (8.3°C) 0.86 0.92 0.88 0.93
48°F (8.9°C) 0.79 0.88 0.82 0.89
49°F (9.4°C) 0.74 0.83 0.77 0.85