Technical data

Optional Factory-Installed Features—Evaporator/Chilled Water & Condensing Units
4
3.0 OPTIONAL FACTORY-INSTALLED FEATURES—EVAPORATOR/CHILLED WATER &
CONDENSING UNITS
3.1 Electric Reheat
Electric low watt tubular reheat element with non-corrosive metal sheath provides one stage of non-
ionizing reheat to maintain room dry bulb temperature.
3.2 Humidifier/Electric Reheat Package
The humidifier and electric reheat are available as a package for complete humidity control. The can-
ister humidifier includes a steam-generating type humidifier with automatic flushing circuit, inlet
strainer, drain, 1" (25.4mm) air gap on fill line and solenoid valves. Humidifier problem alarm annun-
ciates at the wall-mounted display panel. Maximum humidifier water supply pressure is 150psi
(1034kPa).
3.3 Optional Configurations—Prop Fan Condensing Units
Outdoor Prop Fan Condensing Units are also available in the following optional configurations:
High ambient models for providing catalog capacities at ambient temperatures up to 105°F (40°C)
- 2- and 3-ton models only.
Quiet-Line models for low noise level conditions (below 56 dBA) and for providing catalog capaci-
ties at ambient temperatures up to 95°F (35°C) - 2- and 3-ton models only.
Condenser coils can be phenolic-coated for extended coil life in coastal areas.
3.4 Optional Configurations—Indoor Remote Water/Glycol Condensing Units
Indoor Remote Water/Glycol Condensing Units are also available with the following piping options:
Two-way water regulating valve with 350psi (2413kPa) design pressure.
Three-way water regulating valve with 150psi (1034kPa) design pressure.
Three-way water regulating valve with 350psi (2413kPa) design pressure.