Technical data

Chapter 2 Model Configuration 5
DataMate 3000 Series Air Conditioner Technical Manual
14
13
9
15
426 ± 1
35
20
15
11
50
24
1750 ± 15 (blue)
1600 ± 15 (brown)
12
2345678
1
10
Figure 2-4 Dimensions of heater (unit: mm)
2.3 Units Configuration
Table 2-2 Configuration Table Of Indoor Units And Outdoor Units
Indoor Unit Outdoor Unit
Model
Series
Main Power
Supply
Capability
Rate
Cooling Only With Reheat
With Humidifier
And Reheat
Standard Lee-Temp
5kW DME05WCE1 DME05WOE1 -- DMC07W1 DML07W1DME3000
S Series
220V/1
Ph/50Hz
7kW DME07WCE1 DME07WOE1 -- DMC07W1 DML07W1
7kW DME07MC1 DME07MO1 DME07MH1 DMC07W1 DML07W1DME3000
Standard
380V/3
Ph/50Hz
12kW DME12MC1 DME12MO1 DME12MH1 DMC12W1 DML12W1
2.4 Refrigeration circuit
The compressor (1) pumps the hot gaseous refrigerant into an outdoor air – cooled condenser (2). The liquefied
refrigerant flows through the thermostatic expansion valve (3) and then arrives to the evaporator (5). Here the
refrigerant, thanks to the heat –exchanged with the room air moved by the fan (5).-evaporates and returns to the
compressor (1); From this, the refrigerant begins a new refrigeration cycle. To maintain the correct refrigerant
discharge pressure, the speed of the motor fan (6) is controlled (on-off or an optional rate).
The compressor (1) has a crankcase heater to avoid return of liquid return of liquid refrigerant from the condenser in
summertime, thus protecting the compressor from undesired refrigerant slugging during the start up.
Figure 2-5 System Elements Drawing