Technical data
4 Chapter 2 Model Configuration
DataMate 3000 Series Air Conditioner Technical Manual
The shadow in Figure 2-1 indicates a reasonable service access area. The indoor units can be installed against a wall.
Air conditioners with heaters should keep a distance of minimum 150mm from combustible substance. When testing
the air conditioner, the exterior fine pressure should be kept below 150Pa lest the air quantity should be low and the
heater should overheat,
The mechanical parameters of the outdoor units are shown in Figure 2-2, Figure 2-3 and Table 2-1.
626
3
5
3
7
0
2
3
5
3
7
0
2
1238
Figure 2-2 Dimensions of standard outdoor units (unit: mm)
3
5
3
70
2
2
5
0
5
7
5
1
2
3
8
2
5
0
5
7
5
3
53
626
702
Figure 2-3 Dimensions of Lee Temp outdoor units (unit: mm)
Table 2-1 Mechanical parameters of units
Parameters
Models
Cooling capacity
(kW)
Dimensions
(W*D*H) (mm)
Net weight (kg)
DME05W 5.5
510
×
386
×
1740
80
DME07W 7.5
510
×
386
×
1740
85
DME07M 7.5
600
×
550
×
1900
150
DME12M 12.5
600
×
550
×
1900
160
DMC07 -
702
×
353
×
626
34
DMC12 -
702
×
353
×
1238
58
DML07 -
952
×
353
×
626
53
DML12 -
952
×
353
×
1238
95
The dimensions of the heater (optional parts) are illustrated below.