Technical data
Chapter 5 Microprocessor Control 17
DataMate 3000 Series Air Conditioner Technical Manual
1. Use Up/Down buttons to move the cursor to Teamwork in the System Setup menu, and press Enter to display the
Teamwork sub-menu, as shown in Figure 5-26. Use Up/Down buttons to move the cursor to Cntl Board, and press
Enter to set the control board number for communication with other control boards. It can be set from 0 to 15, and the
default value is 0. Use Up/Down buttons to move the cursor to Unit No, and press Enter to set the unit number. It can
be set from 0 to 15, and the default value is 0.
Cntl Board
Unit NO
1
1
Figure 5-26 Teamwork sub-menu
2. Use Up/Down buttons to move the cursor to Start Delay in the System Setup menu, and press Enter to display the
sub-menu, as shown in Figure 5-27. The default values and the setting ranges of the delays in Figure 5-27 are listed in
Table 5-1.
Cold Start
Hot Start
Main Fan
Cp Start
180s
10s
30s
90s
Cp MinOn
Cp MinOff
LP Switch
180s
180s
180s
Figure 5-27 Start Delay sub-menu
3. Press Up/Down buttons to move the cursor to C/F Degrees in the System Setup menu, and press Enter to set the
displayed temperature unit to Celsius (°C) or Fahrenheit (°F). The default unit is Celsius scale.
4. Use Up/Down buttons to move the cursor to Hum Control in the System Setup menu and press Enter to set the
humidity control method to absolute humidity control or relative humidity control. The default method is relative
humidity control.
5. Use Up/Down buttons to move the cursor to Beeper in the System Setup menu, and press Enter to set the beeper to
ON or OFF. The default is ON.
6. Use Up/Down buttons to move the cursor to Backlight in the System Setup menu, and press Enter to set the
backlight to ON or OFF. The default setting is ON.
7. Use Up/Down buttons to move the cursor to Contrast in the System Setup menu, and press Enter to set the contrast
of the LCD. The setting range is from 28% to 38%, and the default setting is 30%.
5.9.2 Select Options
The optional function settings will not be lost when power fails. Select Options from the System Menu to display the
functions listed in Figure 5-28.
Heat
Hum
NewFlow
Standby
OFF
OFF
OFF
Figure 5-28 Select Options menu
1. Use Up/Down buttons to move the cursor to Heat, and press Enter to set the optional heater to ON or OFF. The
default setting is OFF.
2. Use Up/Down buttons to move the cursor to Hum, and press Enter to set the optional humidifier to ON or OFF. The
default setting is OFF.
3. Use Up/Down buttons to move the cursor to NewFlow, and press Enter to set the new flow to ON or OFF. The
default setting is OFF.
4. Use Up/Down buttons to move the cursor to Standby, and press Enter to display the Standby sub-menu, as shown
in Figure 5-29.