Technical data
6 Chapter 2 Model Configuration
DataMate 3000 Series Air Conditioner Technical Manual
Chapter 3 Operation Range
DME3000 are provided for operating within the following working ranges:
Table 3-1
horizontal
≤
50m
Installing position between indoor unit
and outdoor unit
vertical
Δ
H
(1)
:
-5m
≤Δ
H
≤
20m
temperature 0°C ~30°C
Room air conditions
humidity
30
%
~80
%
RH
standard outdoor unit
-15°C ~
+
45°C
Ambient temperature
with Lee-Temp unit
-34°C ~
+
45°C
Altitude
<
1000m
(2)
voltage
-15
%
~
+
15
%
(3)
Power supply tolerances
frequency
±
2Hz
entironment Indoor, clean (without dust)
temperature -40°C ~70°C
humidity
5
%
~95
%
RH
Storage conditions
storage hours
<
6 months
(4)
Notes:
1) ΔH = the altitude of outdoor unit - the altitude of indoor unit;
2) The system should be derated where the altitude is higher than 1000m;
3) The error (because of sensors) in 3% is permitted;
4) The shipment and storage time should not exceed 6 months. Otherwise, the system shall be re-tested.










